Page 65

background image

Ethernet Communication Module IFD9507

DVP-PLC Application Manual

63

3. Select “Static” in IP Configuration.

4. Enter “192.168.1.99” in IP Address field.

5. Enter “255.255.255.0” in Netmask field.

6. Select “Ethernet/IP” in Application Protocol.

7. Enter “231” in Station Address.

8. Press

“OK”.

9. Open

DCISoft

“Ethernet/IP” configuration screen.

10. Enter AB PowerFlex 40P IP Address“192.168.1.72” in Dest IP Field.

11. Select “Cyclic” in Trigger.

12. Enter PowerFlex 40P parameter “1”,”4”,”2”,”2”,”2 byte”,”6” in In Instance, In Size, Out Instance, Out

Size, Width, Config Instance in turn.

13. Press “OK”.

„

WPL

program

1. Write control data to DVP IFD9507 IN register (H0500)

2. Use WPL MODWR instruction to write the control data to EIP (H0500).

3. Ex.

RUN:111000000011010ÆH701A

STOP:111000000011001ÆH7019

Reverse RUN:111000000101010ÆH702A

4. Select which communication index you want. Write 1~4 to DVPIFD9507 BR15 (H000F).

Use WPL MODWR instruction to select the DVP IFD9507 BR (H0500) index.

5. Set the I/O Enable Flag (BR14).