Ethernet Communication Module IFD9507

DVP-PLC Application Manual

16

b15 b14 b13 b12

b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

Device

16

Device

15

Device

14

Device

13

Device

12

Device

11

Device

10

Device

9

Device

8

Device

7

Device

6

Device

5

Device

4

Device

3

Device

2

Device

1

M B # 2 1 4 : M o n i t o r e d Sta t u s

Explanations:

Every MB records the status in the 16-bit device. 1 = normal; 0 = abnormal.

b15 b14 b13 b12

b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

Device

16

Device

15

Device

14

Device

13

Device

12

Device

11

Device

10

Device

9

Device

8

Device

7

Device

6

Device

5

Device

4

Device

3

Device

2

Device

1

5.2 Monitor Word Registerss (MW)

MW#

Attribute

Content

Explanation

Default Latched

0 R/W

Number of devices

monitored

Cache mode normally enabled (b15=1),
monitoring data in max. 16 slaves.

0 YES

1 R/W

No. of station
monitored

No. of the station to be monitored

0

YES

2 R/W

Address of the
device monitored

Recording the address of the device
monitored

0 YES

3 ~ 32

R/W

No. of station
monitored, address
of the device
monitored

No. of the station to be monitore; recording
the address of the device monitored.

0 YES

33 ~ 200

R/W

Reserved

201 ~ 216

R

Monitored value

Every MW records the monitored value in 1
register

0 NO

216 ~ 300

R

Reserved

301 R

Monitored

status

Every MW records the status in a 16-bit
register. 1 = normal; 0 = abnormal

0 NO

Symbol “R” refers to read only; “R/W” refers to read and write.

M W # 0 : N u m b e r o f D e vi c e s M o n i t o r e d

Explanations:

For setting up the number of devices to be monitored. Max. data in 16 slaves can be monitored.

b15 is read only (Default =1: normally enabled cache mode)

M W # ( O d d N u m b e r ) : N o . o f Sta t i o n M o n i t o r e d

Explanations:

MW#1, MW#3, MW#5…MW#33 are for setting up the station No. (0 ~ 255) to be monitored.

M W # ( E ve n N u m b e r ) : A d d r e s s o f D e vi c e M o n i t o r e d

Explanations:

MW32, MW34, MW#36…MW#34 are for setting up the address of the device to be monitored.

M W # 2 0 1 ~ # 2 1 6 : M o n i t o r e d Va l u e