Ethernet communication module ifd9507 – Delta Electronics Ethernet Communication Module IFD9507 User Manual
Page 22
![background image](/manuals/74887/22/background.png)
Ethernet Communication Module IFD9507
DVP-PLC Application Manual
20
Object Name
Class ID Code Instance Code
Function
Description
Object Type Attribute
TCP Link
0xF6
0x01
TCP/IP Link
Object
Object Get
9.3 CIP General Status Code (Reference Volume 1:CIP Common Specification Appendix B)
General
Status Code
(in hex)
Status Name
Description of Status
00 Success
Service
was
successfully
performed by the object specified.
01
Connection failure
A connection related service failed along the connection path.
02
Resource unavailable
Resources needed for the object to perform the requested
service were unavailable
04
Path segment error
The path segment identifier or the segment syntax was not
understood by the processing node. Path processing shall stop
when a path segment error is encountered.
05 Path
destination
unknown
The path is referencing an object class, instance or structure
element that is not known or is not contained in the processing
node. Path processing shall stop when a path destination
unknown error is encountered.
08
Service not supported
The requested service was not implemented or was not
defined for this Object Class/Instance.
09
Invalid attribute value
Invalid attribute data detected
0E
Attribute not settable
A request to modify a non-modifiable attribute was received.
13
Not enough data
The service did not supply enough data to perform the
specified operation.
14
Attribute not supported The attribute specified in the request is not supported
15
Too much data
The service supplied more data than was expected
16
Object does not exist
The object specified does not exist in the device.
20
Invalid parameter
A parameter associated with the request was invalid. This code
is used when a parameter does not meet the requirements of
this specification and/or the requirements defined in an
Application Object Specification.
26
Path Size Invalid
The size of the path which was sent with the Service Request
is either not large enough to allow the Request to be routed to
an object or too much routing data was included.
9.4 Connection Manager Service Request Error Codes (Reference Volume 1:CIP Common Specification
Table3-5.29)
General
Status
Extended Status
Explanation and Description
0x00
Service
completed
successfully
0x01
0x0100
CONNECTION IN USE OR DUPLICATE FORWARD OPEN
This extended status code shall be returned when an originator is
trying to make a connection to a target with which the originator may
have already established a connection
0x01
0x0103
TRANSPORT CLASS AND TRIGGER COMBINATION NOT
SUPPORTED
A transport class and trigger combination has been specified which
is not supported by the target. Routers shall not fail the connection
based on the transport class and trigger combination. Only targets
shall return this extended status code.
0x01
0x0108
INVALID NETWORK CONNECTION PARAMETER
This extended status code shall be returned as the result of
specifying a connection type, connection priority, redundant owner
or fixed / variable that is not supported by the target application.
Only a target node shall return this extended status code.