Ethernet Communication Module IFD9507

DVP-PLC Application Manual

17

Explanations:

Every MW records the values in 1 register.

MW#201 MW#202 MW#203 MW#204 MW#205 MW#206 MW#207 MW#208 MW#209 MW#210

Device 1 Device 2 Device 3 Device 4 Device 5 Device 6 Device 7 Device 8 Device 9 Device 10

MW#211 MW#212 MW#213 MW#214 MW#215 MW#216

Device

11

Device

12

Device

13

Device

14

Device

15

Device

16

M W # 3 0 1 : M o n i t o r e d Sta t u s

Explanations:

Every MW records the status in a 16-bit register. 1 = normal; 0 = abnormal.

b15 b14 b13 b12 b11 b10

b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

Device

16

Device

15

Device

14

Device

13

Device

12

Device

11

Device

10

Device

9

Device

8

Device

7

Device

6

Device

5

Device

4

Device

3

Device

2

Device

1

6

Setting up Device Address and Relay Address in Slave Mode (For Modbus TCP protocol
only)

MIP#

Attribute

Content

Explanation

Default

Latched

0 ~ 50

R/W

Corresponding
address

Max. 100 addresses are allowed. High
byte for 1 address and low byte for 1
address.

0 Yes

50 ~ 249

R/W

Relay IP address

Total 100 IPs. Every address (1 byte)
corresponds to 1 IP address (4 bytes).

0 Yes

Symbol “R” refers to read only; “R/W” refers to read and write.

M I P # 0 : C o r r e s p o n d i n g A d d r e s s

Explanations:

The low bytes of MIP#0 are for the first address, and the high byte are for the second address, and so on.

M I P # 5 1 ~ # 5 2 : C o r r e s p o n d i n g I P f o r t h e 1

s t

D e vi c e A d d r e s s

Explanations:

Example 1: If you wish to convert “192.168.0.1” into C0A80001 (hex), write A8C0 into MIP50 and H0100 into

MIP51.

Example 2: Data in address 1 have to correspond to 192.168.0.8. Data in address 2 have to correspond to

192.168.0.6. To complete such settings, write H0102 into MIP0, H0800 into MIP50, HA8C0 into MIP51, H0600

into MIP52, and HA8C0 into MIP53.

7

Setting up Device Address and Other Network Settings in Slave Mode

Parameter

Explanation

Device address

Address of Modbus device

Relay IP address

Corresponding IP address for a device

Priority/Time Tick

Scale of time. Unit: ms

Timeout Tick

Scale of timeout

Timeout

Timeout = Time Tick × Timeout Tick (Unit: ms)