Ethernet Communication Module IFD9507

DVP-PLC Application Manual

15

4.5 Out buffer registers (OUT) in IFD9507

OUT# Attribute

Content

Explanation

Default

Latched

0~255

R

Data output buffer

0

No

Symbol “R” refers to read only; “R/W” refers to read and write.

Explanations:

The output data was sent to RS-485.

5 Monitoring

Functions

5.1 Monitor Bit Registers (MB)

MB#

Attribute

Content

Explanation

Default

Latched

0 R/W

Number of devicees
monitored

Cache mode normally enabled (b15=1),
monitoring data in max. 16 slaves.

0 Yes

1 R/W

No. of station
monitored

No. of the station to be monitored

0

Yes

2 R/W

Address of the
device monitored

Recording the address of the device
monitored.

0 Yes

3 ~ 32

R/W

No. of station
monitored, address
of the device
monitored

No. of the station to be monitored;
recording the address of the device
monitored.

0 Yes

33 ~ 200

R/W

Reserved

201 R

Monitored

value

Every MB records the value in the 16-bit
device.

0 No

202 ~ 213

R

Reserved

214 R

Monitored

status

Every MB records the status in the 16-bit
device. 1 = normal; 0 = abnormal

0 No

Symbol “R” refer to read only; “R/W” refers to read and write.

M B # 0 : N u m b e r o f D e vi c e s M o n i t o r e d

Explanations:

For setting up the number of devices to be monitored. Max. data in 16 slaves can be monitored.

b15 is read only (Default =1: normally enabled cache mode)

M B # ( O d d N u m b e r ) : N o . o f Sta t i o n M o n i t o r e d

Explanations:

MB#1, MB#3, MB#5…MB#33 are for setting up the station No. (0 ~ 255) to be monitored.

M B # ( E ve n N u m b e r ) : A d d r e s s o f D e vi c e M o n i t o r e d

Explanations:

MB#2, MB#4, MB#6…MB#34 are for setting up the address of the device to be monitored.

M B # 2 0 1 : M o n i t o r e d Va l u e

Explanations:

Every MB records the values in the 16-bit device.