Ethernet communication module ifd9507 – Delta Electronics Ethernet Communication Module IFD9507 User Manual
Page 14
![background image](/manuals/74887/14/background.png)
Ethernet Communication Module IFD9507
DVP-PLC Application Manual
12
B R # 5 : B a u d R a t e
Explanations:
BR#5 low byte for baud rate of COM1
Communication
interface
Explanation
Data
Baud rate
(bps)
Data
Baud rate
(bps)
Data
Baud rate
(bps)
0x01 110 0x06 2,400 0x0B
57,600
0x02 150 0x07 4,800 0x0C
115,200
0x03 300 0x08 9,600
0x04 600 0x09
19,200
Content
RS-232
0x05 1,200 0x0A 38,400
BR#5 high byte for baud rate of COM2
Content
RS-485 same as low byte
B R # 6 : A d d r e s s
Explanations:
For filling in or reading the Modbus address. The address will be displayed in the message display after being
set up.
B R # 7 : N u m b e r o f D I / D O P o i n ts
Explanations:
Read the number of DI/DO points from BR#7.
B R # 9 : E r r o r C o d e
Explanations:
Error code = 0 refers to no error occurring.
Code
Indication
How to correct
01 ~ F7
Node address of the scan module
(when operating normally)
--
F0
Returning to default setting
--
F1
IFD9507 being powered
--
F2
Power supply in low voltage
Check if the power supply of the module works normally.
F3
Internal memory detection error
1. Re-power IFD9507. If the error still exists, try step 2.
2. Reset IFD9507. If the error still exists, send the
module back to the factory for repair.
F4
Internal error. Manufacturing error.
1. Re-power IFD9507. If the error still exists, try step 2.
2. Reset IFD9507. If the error still exists, send the
module back to the factory for repair.
F5
Network connection error
Check if IFD9507 is connected normally to the network.
F6
Full number of devices connected
in the network.
Check if the number is too much.
F7 UART
setting
error.
Check if the RS-485, RS-232 communication format is
correct.
E1
Alarm 1 triggered
Check alarm input point 1.