Ethernet Communication Module IFD9507

DVP-PLC Application Manual

12

B R # 5 : B a u d R a t e

Explanations:

BR#5 low byte for baud rate of COM1

Communication

interface

Explanation

Data

Baud rate

(bps)

Data

Baud rate

(bps)

Data

Baud rate

(bps)

0x01 110 0x06 2,400 0x0B

57,600

0x02 150 0x07 4,800 0x0C

115,200

0x03 300 0x08 9,600

0x04 600 0x09

19,200

Content

RS-232

0x05 1,200 0x0A 38,400

BR#5 high byte for baud rate of COM2

Content

RS-485 same as low byte

B R # 6 : A d d r e s s

Explanations:

For filling in or reading the Modbus address. The address will be displayed in the message display after being

set up.

B R # 7 : N u m b e r o f D I / D O P o i n ts

Explanations:

Read the number of DI/DO points from BR#7.

B R # 9 : E r r o r C o d e

Explanations:

Error code = 0 refers to no error occurring.

Code

Indication

How to correct

01 ~ F7

Node address of the scan module
(when operating normally)

--

F0

Returning to default setting

--

F1

IFD9507 being powered

--

F2

Power supply in low voltage

Check if the power supply of the module works normally.

F3

Internal memory detection error

1. Re-power IFD9507. If the error still exists, try step 2.
2. Reset IFD9507. If the error still exists, send the

module back to the factory for repair.

F4

Internal error. Manufacturing error.

1. Re-power IFD9507. If the error still exists, try step 2.
2. Reset IFD9507. If the error still exists, send the

module back to the factory for repair.

F5

Network connection error

Check if IFD9507 is connected normally to the network.

F6

Full number of devices connected

in the network.

Check if the number is too much.

F7 UART

setting

error.

Check if the RS-485, RS-232 communication format is
correct.

E1

Alarm 1 triggered

Check alarm input point 1.