beautypg.com

Ethernet communication module ifd9507 – Delta Electronics Ethernet Communication Module IFD9507 User Manual

Page 16

background image

Ethernet Communication Module IFD9507

DVP-PLC Application Manual

14

AL#

Attribute

Content

Explanation

Default

Latched

1

R/W

Alarm point 2

0

Yes

2

R/W

Alarm point 3

0

Yes

Symbol “R” refer to read only; “R/W” refers to read and write.

A L # 0 : A l a r m P o i n t 1

Explanations:

You can designate one RX extension point as the alarm point by setting up the AL register in IFD9507. When

the alarm point is triggered, IFD9507 will execute its corresponding function. When b15 of AL0 is set as “1”,

the Gateway will execute the event immediately. When RX point is triggered, the Gateway will only execute

the triggered event once.

Device

Function

Setting

Attribute Default Latched

b15

Enabling the
function

b15 = 1: Enabling
b15 = 0: Disabling

R/W 0 Yes

b4 ~ b14 Reserved

R/W 0 No

b2 ~ b3

Type of event
enabled when
RX alarm point
is triggered

b3

b2

Reserved 0

0

Trigger E-Mail

0

1

Reserved 1

0

Reserved 1

1

The setting will be invalid when

thealarm function is being executed.

R/W 0 Yes

b1

Reserved Reserved

AL#0

b0

Condition for
triggering RX

b0 = 0: Triggered when RX input

point is low

b0 = 1: Triggered when RX input

point is high

R/W 0 Yes

A L # 1 : A l a r m O u t p u t 2

Explanations:

The settings for AL#1 are the same as those in AL#0.

A L # 2 : A l a r m O u t p u t 3

Explanations:

The settings for AL#2 are the same as those in AL#0.

4.4 In buffer registers (IN) in IFD9507

IN#

Attribute

Content

Explanation

Default

Latched

0~255

R/W

Data input buffer

Ethernet/IP input data

0

No

Symbol “R” refers to read only; “R/W” refers to read and write.

Explanations:

The input data was sent to Ethernet.