Technical details
Operating Manual PSSu E S 2AI U(T)
21405EN03
39
Analogue inputs
312440
314440
Measuring ranges
Type
Singleended
Singleended
Measuring range
0 10 V
0 10 V
Type
Differen
tial input Differential input
Measuring range
0 10 V
0 10 V
Type
Differen
tial input Differential input
Measuring range
10 10 V
10 10 V
Input filter
RC filter
RC filter
Cutoff frequency
130 Hz
130 Hz
Voltage measurement
Input resistance
100 kOhm
100 kOhm
Max. continuous voltage
12 V
12 V
Resolution (without sign bit)
12 Bit
12 Bit
Max. common mode voltage
5 V
5 V
Deviations from the measuring
range limit value
Linearity error
0,05 %
0,05 %
Output variable error at 25 °C
0,2 %
0,2 %
Temperature coefficient
0,0200 %/K
0,0200 %/K
Max. measurement error during
EMC test
1,0 %
1,0 %
Potential isolation between input
and periphery supply
Yes
Yes
Typ. processing time of the ana
logue input
1,0 ms
1,0 ms
Inputs
312440
314440
Potential isolation between input
and internal module bus voltage
Yes
Yes
Environmental data
312440
314440
Climatic suitability
EN 6006821, EN 60068214, EN
6006822, EN 60068230, EN
60068278
EN 6006821, EN 60068214, EN
6006822, EN 60068230, EN
60068278
Ambient temperature
In accordance with the standard EN 60068214
EN 60068214
Temperature range
0 60 °C
40 70 °C
Storage temperature
In accordance with the standard EN 6006821/2
EN 6006821/2
Temperature range
25 70 °C
40 70 °C
Climatic suitability
In accordance with the standard EN 60068230, EN 60068278
EN 60068230, EN 60068278
Humidity
93 % r. h. at 40 °C
93 % r. h. at 40 °C
Condensation during operation
Not permitted
Shortterm
EMC
EN 6100042, EN 6100043, EN
6100044, EN 6100045, EN
6100046, EN 6100062, EN
6100064
EN 6100042, EN 6100043, EN
6100044, EN 6100045, EN
6100046, EN 6100062, EN
6100064