Function description
Operating Manual PSSu E S 2AI U(T)
21405EN03
17
4.2.3.3
Manufacturer scaling
The manufacturer scaling is used to define the offset (zero point compensation) and gain
(amplification) of the digital signal.
Manufacturer scaling active (default setting)
}
Default values for manufacturer scaling:
–
Offset (b
1
): 0
–
Gain (a
1
): 8194
D
(2002
H
)
INFORMATION
The default setting for gain (a
1
) means an amplification factor of 8.
The digital value after manufacturer scaling is calculated using the following for
mula:
}
y = (a
1
/ 1024
D
* x) + b
1
or
}
y = (a
1
/ 400
H
* x) + b
1
Legend:
}
y: Digital value after manufacturer scaling
}
x: Digital value before manufacturer scaling
}
a
1
: Gain
}
b
1
: Offset
}
a
1
/ 1024
D
: Amplification factor
INFORMATION
With the given amplification factor, gain (a
1
) is calculated as follows:
Gain (a
1
) = Amplification factor * 1024
D
Amplification by 5 % is therefore:
1.05 * 1024
D
= 1075
D
Arithmetic examples using decimal values:
Digital value
before manu
facturer scaling
(x)
Gain (a
1
)
Offset (b
1
)
Amplification
factor (a
1
/ 1024
D
)
Value after
manufacturer
scaling (y)
1 000
1 024
0
1
1 000
1 000
2 048
0
2
2 000
1 000
8 192
0
8
8 000
1 000
1 075
500
1.05
1 550
1 000
512
50
0.5
450