Function description

Operating Manual PSSu E S 2AI U(­T)
21405­EN­03

17

4.2.3.3

Manufacturer scaling

The manufacturer scaling is used to define the offset (zero point compensation) and gain
(amplification) of the digital signal.

Manufacturer scaling active (default setting)

}

Default values for manufacturer scaling:

Offset (b

1

): 0

Gain (a

1

): 8194

D

 (2002

H

)

INFORMATION

The default setting for gain (a

1

) means an amplification factor of 8.

The digital value after manufacturer scaling is calculated using the following for­
mula:

}

y = (a

1

 / 1024

D

 * x) + b

1

 or

}

y = (a

1

 / 400

H

 * x) + b

1

Legend:

}

y: Digital value after manufacturer scaling

}

x: Digital value before manufacturer scaling

}

a 

1

: Gain

}

b 

1

: Offset

}

a 

1

 / 1024

D

: Amplification factor

INFORMATION

With the given amplification factor, gain (a

1

) is calculated as follows:

Gain (a

1

) = Amplification factor * 1024

D

Amplification by 5 % is therefore:
1.05 * 1024

D

 = 1075

D

Arithmetic examples using decimal values:

Digital value
before manu­
facturer scaling
(x)

Gain (a

1

)

Offset (b

1

)

Amplification
factor (a

1

 / 1024

D

)

Value after
manufacturer
scaling (y)

1 000

1 024

0

1

1 000

1 000

2 048

0

2

2 000

1 000

8 192

0

8

8 000

1 000

1 075

500

1.05

1 550

1 000

512

­50

0.5

450