beautypg.com

7 summary and overview, Summary and overview – Pilz PSSu E S 2AI U User Manual

Page 22

background image

Function description

Operating Manual PSSu E S 2AI U(­T)
21405­EN­03

22

Input

PII

Assignment

Input I0

1

LSB status byte

...

...

8

MSB status byte

Input I1

9

LSB status byte

...

...

16

MSB status byte

4.2.7

Summary and overview

The module has the following configuration options:

Default
value

Meaning

Input area

0

0 V … 10 V, single­pole, referenced to earth (single­
ended)
(1 = 0 ... +10 V dual­pole, differential input)
(2 = ­10 V ... +10 V dual­pole, differential input)

Manufacturer scaling active

1/TRUE

Activated

Manufacturer scaling offset

0

Offset: Magnitude 0

Manufacturer scaling gain

8194

D

8x amplification, displaced three bit places

User scaling active

0/FALSE

deactivated

User scaling offset

0

Offset: Magnitude 0

User scaling gain

256

D

1x amplification, signal unchanged

Filter active

0/FALSE

deactivated

Filter characteristic

0

2nd order FIR filter

Range monitoring active

1/TRUE

Activated

Upper limit value

4095

D

Upper limit of number range

Lower limit value

­4095

D

Lower limit of number range

Limit value 1 active

0/FALSE

deactivated

Limit value 1

­32 767

D

Lower limit of number range

Limit value 2 active

0/FALSE

deactivated

Limit value 2

32 767

D

Upper limit of number range

Sign and magnitude representa­
tion active

0/FALSE

Deactivated; two's complement is activated

Output ADC raw value only

0/FALSE

deactivated

ADC initialisation value

4096

 D

4096

 D

 (1000

H

) is issued when no data is detected.

This manual is related to the following products: