7 summary and overview, Summary and overview – Pilz PSSu E S 2AI U User Manual
Page 22

Function description
Operating Manual PSSu E S 2AI U(T)
21405EN03
22
Input
PII
Assignment
Input I0
1
LSB status byte
...
...
8
MSB status byte
Input I1
9
LSB status byte
...
...
16
MSB status byte
4.2.7
Summary and overview
The module has the following configuration options:
Default
value
Meaning
Input area
0
0 V … 10 V, singlepole, referenced to earth (single
ended)
(1 = 0 ... +10 V dualpole, differential input)
(2 = 10 V ... +10 V dualpole, differential input)
Manufacturer scaling active
1/TRUE
Activated
Manufacturer scaling offset
0
Offset: Magnitude 0
Manufacturer scaling gain
8194
D
8x amplification, displaced three bit places
User scaling active
0/FALSE
deactivated
User scaling offset
0
Offset: Magnitude 0
User scaling gain
256
D
1x amplification, signal unchanged
Filter active
0/FALSE
deactivated
Filter characteristic
0
2nd order FIR filter
Range monitoring active
1/TRUE
Activated
Upper limit value
4095
D
Upper limit of number range
Lower limit value
4095
D
Lower limit of number range
Limit value 1 active
0/FALSE
deactivated
Limit value 1
32 767
D
Lower limit of number range
Limit value 2 active
0/FALSE
deactivated
Limit value 2
32 767
D
Upper limit of number range
Sign and magnitude representa
tion active
0/FALSE
Deactivated; two's complement is activated
Output ADC raw value only
0/FALSE
deactivated
ADC initialisation value
4096
D
4096
D
(1000
H
) is issued when no data is detected.