4 function description, 1 module features, 1 functions – Pilz PSSu E S 2AI U User Manual
Page 12: 2 integrated protection mechanisms, 2 configuration, Section 4, Function description, Module features, Functions, Integrated protection mechanisms

Function description
Operating Manual PSSu E S 2AI U(T)
21405EN03
12
4
Function description
4.1
Module features
4.1.1
Functions
The module supply provides the module with voltage.
The input signals are read in, analogue prefiltered and converted into digital signals. The
resolution is 12 bits (4095 steps) and is converted into a 16 Bit value. Additional signal pro
cessing can be defined using the system software (see schematic representation of signal
processing). The individual steps are described in the "Configuration" section.
The input signals are transmitted to the head module via the ST module bus. As an option
the input module can send status information for each input.
All the configuration data is stored in the head module and is assigned to the input module
on restart. This way the configuration data is retained even if you change the input module.
Schematic representation of signal processing:
IN
ADC
Filter
Limit
values
Data
format
ST
module
bus
Manufact.
scaling
User
scaling
4.1.2
Integrated protection mechanisms
When the PSSu E F PS1(T) is used to supply the system, the module supply is buffered
for 20 ms if the supply voltage is interrupted.
The module detects the following errors:
}
Startup error
}
Configuration error
}
ST communication error
}
Bus termination error
4.2
Configuration
The following options exist for configuring the module in system environment A:
}
Via a fieldbus without the modular device description file
Without the modular device description file it is only possible to configure the input or
output range. All other configuration details have default values.