beautypg.com

3 connecting the module, Connecting the module – Pilz PSSu E S 2AI U User Manual

Page 34

background image

Wiring

Operating Manual PSSu E S 2AI U(­T)
21405­EN­03

34

Base module

Terminal configuration

Screw terminals:
PSSu BP­C 1/8S
PSSu BP­C 1/8S­T

Cage clamp terminals:
PSSu BP­C 1/8C
PSSu BP­C 1/8C­T

With C­rail:

11: Input I0+

21: Input I1+

12­22: 0 V analogue
(12­22 linked within the base
module)

13­23: C­rail supply,
cable screening
(13­23 linked within the base
module)

14: Input I0­

24: Input I1­

21

11

22

12

23

13

24

14

6.3

Connecting the module

Input circuit

Without C­rail

With C­rail

Voltage range 0 ... +10 V
single­pole, referenced to earth

21

11

22

12

23

13

24

14

0 V

I0+

I0-

I1+

I1-

0 V

21

11

22

12

23

13

24

14

0 V

I0+

I0-

I1+

I1-

0 V