7.3

CANopen object description

7

Operation

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

7-8

7.3.2

Device profile

Device profile

7-

][BA_Betrieb CANopen Gerte

In accordance with CiA 401 Device Profile for Generic I/O Modules Ver-

sion 3.0

Object

Index

Description

8-Bit Digital Input

6000

Digital input data: Grouping 8 input channels into one byte

Global Interrupt Enable

6005

Global interrupt enable, without having to adapt the interrupt masks

Interrupt Mask Any Change 8-Bit

6006

Specifies which I/O channels trigger an interrupt at any signal change.

Interrupt Mask Low-to-High 8-Bit

6007

Specifies which I/O channels trigger an interrupt when the signal
changes from low to high.

Interrupt Mask High-to-Low 8-Bit

6008

Specifies which I/O channels trigger an interrupt when the signal
changes from high to low.

8-Bit Digital Output

6200

Digital output data: Grouping 8 output channels into one byte

Error Mode Output 8-Bit

6206

Defines whether an output is to assume a predefined error value in the
case of an error or "Stop Remote Node".

Error Value Output 8-Bit

6207

If the corresponding error mode is activated, the outputs are set to the
preset values in the case of an error.

Analogue Input 16-Bit

6401

Object for up to 16 Bit wide analogue input values

Analogue Input Interrupt Trigger Se-
lection

6421

Determines the events/triggers that initiate an interrupt for a specific
channel.

Analogue Input Interrupt Source

6422

Determines which channels have triggered an interrupt.

Analogue Input Global Interrupt Ena-
ble

6423

Global interrupt enable, without having to adapt the interrupt masks

Analogue Input Interrupt Upper Limit
Integer

6424

If activated, an interrupt is triggered if the input value is equal to or
greater than the specified value.

Analogue Input Interrupt Lower Limit
Integer

6425

If activated, an interrupt is triggered if the input value is lower than the
specified value.

Analogue Input Interrupt Delta Un-
signed

6426

Indicates the relative difference to the last reference value, where an
interrupt is triggered if the value exceeds or drops below that refer-
ence value.

Analog Input Interrupt Negative Delta
Unsigned

6427

Indicates the relative difference to the last reference value, where an
interrupt is triggered if the value drops below that reference value.

Analog Input Interrupt Positive Delta
Unsigned

6428

Indicates the relative difference to the last reference value, where an
interrupt is triggered if that reference value is exceeded.

Analogue Output 16-Bit

6411

Object for up to 16 Bit wide analogue output values

Analogue Output Error Mode

6443

Object defines whether an output is to assume a predefined error val-
ue in the case of an error or "Stop Remote Node".

Analogue Output Error Value Integer

6444

If the corresponding error mode is activated, the outputs are set to the
preset values in the integer format.