Selector switch for setting the transmission rate, 4function description, 2 canopen – Pilz PSSu H CAN User Manual

Page 17

background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

4-3

4.2

CANopen

4

Function description

4.2.2

Selector switch for setting the transmission rate

Selector switch for setting the transmission rate

4-

][Funktionsbeschreibung_BA_Zusatz CAN Übertragung

The transmission rate of a PSSu is set via the “BAUD” DIP switches S1

and S2.

If the PSSu station has lots of telegrams to send via the CANopen field-

bus, make sure that the transmission rate is high enough, e.g. when sev-

eral analogue input/output modules are used. If the transmission rate is

too low, the PSSu may not be able to establish a connection to the

CANopen fieldbus.

“BAUD” DIP switch

Key

Example:

Switch designation

AUTO

500
KBit/s

250
kBit/s

125
kBit/s

Transmission rate
500 kBit/s

S2

OFF

OFF

ON

ON

S1

OFF

ON

OFF

ON

64

Station address

32

16

8

4

2

1

INFORMATION

The transmission rate should only be set when the module is

switched off (no voltage applied).

The settings are only transferred when booting. Any changes

made to the settings during operation will not be transferred.

ADDRESS

OFF ON

S2

S1

32

16

8

4

2

1

BAUD

64