beautypg.com

Autoping commands, Email commands, Vi. command line interface (cli) protocol – SurgeX SX-AX20 User Manual

Page 22: Continued)

background image

Page 21

SX-AX15 (20) User Manual



VI. Command Line Interface (CLI) Protocol

(continued)

AutoPing Commands


Command

Description

Admin

Fact Def

get autoping <1

‐16>

Returns the settings and state of the selected autoping.

Yes

set autoping <1

‐16> ipaddress

Set the IP address of the selected autoping in dotted
decimal.

Yes

0.0.0.0

set autoping <1

‐16> action

Set the action of the selected autoping. On-Follow, On-
Latch, Off-Follow, Off-Latch, Cycle, Cycle-Once, or None.

Yes

None

set autoping <1

‐16> frequency <1‐999>

Set the frequency of the selected autoping in seconds.

Yes

10

set autoping <1

‐16> count <1‐99>

Set the number of failures the selected autoping requires
before it triggers its action.

Yes

3

set autoping <1

‐16> device outlet <1‐8>

Assign an autoping to either a device/outlet or group.

Each autoping can be assigned to one or the other.

Yes

set autoping <1

‐16> group

Yes

Email Commands


Command

Description

Admin

Fact Def

set email enable

Enables or disables the email reporting system.

Yes

No

get email

Returns the current settings of the email client of the root Axess.

Yes

set email server

Set the IP address of an SMTP or ESMTP server.

Yes

0.0.0.0

set email address

Set the return address of the root Axess email client.

Yes

0.0.0.0

set email username

Set the user name for the mail server.

Yes

0.0.0.0

set email password

Set the password for the mail server.

Yes

0.0.0.0

set email retry <1

‐999>

Set the number of retries for failed email reporting.

Yes

3

send test mail

Send a test email to the selected user.

Yes

This manual is related to the following products: