V. Web Server
(continued)
AutoPing View
The AutoPing View displays the 16 AutoPing
channels, their programmed action, and
current status.
The status column displays the current status
of each AutoPing. The numeric column
displays the number of times each AutoPing
has been triggered.
A numeric counter other than 0, with the
status reporting OK, indicates that there have
been previous AutoPing triggers but that the
current status is OK.
To reset the trigger count for any AutoPing,
click the corresponding Reset button.
AutoPing Action
Action Description
None
AutoPing not used
On – Latch
Upon triggering, selected outlet or group will power on and remain so
until manually changed.
On – Follow
Upon triggering, selected outlet or group will power on. When the ping
response returns, outlet or group will power off.
Off – Latch
Upon triggering, selected outlet or group will power off and remain so
until manually changed.
Off – Follow
Upon triggering, selected outlet or group will power off. When the ping
response returns, outlet or group will power on.
Cycle
Upon triggering, Axess will cycle power to selected outlet or group.
Axess will then wait for (Frequency x Fail Count) seconds; if the
response does not return, the power will be cycled again. This will
repeatedly continue until the ping response returns or AutoPing is turned
off. Ensure that the (Frequency x Fail Count) is longer than the time
required to reboot the device.
Cycle Once
Upon triggering, Axess will cycle power to selected outlet or group one
time. It will not automatically cycle power again until the ping response
returns and is lost again.