Vi. command line interface (cli) protocol, Continued) – SurgeX SX-AX20 User Manual
Page 18

Page 17
SX-AX15 (20) User Manual
VI. Command Line Interface (CLI) Protocol
(continued)
Device Commands (continued)
Command
Description
Admin
Fact Def
get voltage
Get the measured line voltage of the local Axess.
Yes
get device <#1
‐#16 | devname> voltage
Get the measured line voltage of the selected Axess.
Yes
set main a vcalibration
Set the voltmeter calibration. From 105.00 to 150.00 in 0.01 V
increments.
Yes
get voltage alarm
High and Low voltage alarms are used to monitor line voltage
conditions and send an alert by email, SNMP and syslog when the
high or low thresholds are exceeded.
High and Low voltage alarms will also result in all outlets being
turned off until the line voltage returns to normal.
Adjustable in 1 V increments.
Yes
Highalarm:
135-150 V
Lowalarm:
90-105 V
get device <#1
‐#16 | devname> voltage alarm
set main a hvalarm
set device <#1
‐#16 | devname> main a
hvalarm
set main a lvalarm
set device <#1
‐#16 | devname> main a
lvalarm
get console
Displays the current console configuration, Timeout, and Baud
Rate.
Yes
set console timeout <30
‐3600 | disable>
Console can be set to automatically logout with no activity for 30
seconds to 1 hr in seconds, or disabled.
Yes
120
set console baudrate
<2400|4800|9600|19200|38400|57600|115200>
The baud rate of the serial port.
400,4800,9600,19200,38400,57600,115200 bps
Yes
115200
get modem
Gets the current settings of the modem. (modem models only)
Yes
set modem countrycode
Sets the modem country code. (modem models only)
See Appendix for a list of country codes.
Yes
181 (USA)