VI. Command Line Interface (CLI) Protocol

(continued)

Device Commands (continued)

Command

Description

Admin

Fact Def

get voltage

Get the measured line voltage of the local Axess.

Yes

get device <#1

‐#16 | devname> voltage

Get the measured line voltage of the selected Axess.

Yes

set main a vcalibration

Set the voltmeter calibration. From 105.00 to 150.00 in 0.01 V
increments.

Yes

get voltage alarm

High and Low voltage alarms are used to monitor line voltage
conditions and send an alert by email, SNMP and syslog when the
high or low thresholds are exceeded.

High and Low voltage alarms will also result in all outlets being
turned off until the line voltage returns to normal.

Adjustable in 1 V increments.

Yes

Highalarm:

135-150 V

Lowalarm:

90-105 V

get device <#1

‐#16 | devname> voltage alarm

set main a hvalarm

set device <#1

‐#16 | devname> main a

hvalarm

set main a lvalarm

set device <#1

‐#16 | devname> main a

lvalarm

get console

Displays the current console configuration, Timeout, and Baud
Rate.

Yes

set console timeout <30

‐3600 | disable>

Console can be set to automatically logout with no activity for 30
seconds to 1 hr in seconds, or disabled.

Yes

120

set console baudrate

<2400|4800|9600|19200|38400|57600|115200>

The baud rate of the serial port.
400,4800,9600,19200,38400,57600,115200 bps

Yes

115200

get modem

Gets the current settings of the modem. (modem models only)

Yes

set modem countrycode

Sets the modem country code. (modem models only)
See Appendix for a list of country codes.

Yes

181 (USA)