SPECIFICATIONS
Number of Channels
32
Input Registers Required
9
Output Registers Required
1
Input Configuration
32 inputs configured in groups of 8 channels per common
LEDs
35 - One each for Ready (Green), Active (Green), Fault (Red),
32 Channel (Green)
Voltage Range
±10VDC, 0 to 10VDC, 0 to 5VDC, 1 to 5VDC
Current Range
4 to 20mA, 0 to 20mA
Impedance, input
Voltage Mode: 10 Megohms, min.
Current Mode: 350 ohms
Fault Detection
Over & under range status bits, for all current and voltage modes.
CMRR
90 dB
Power Requirements
630 mA @ 5 V maximum
Max Input Current
50 mA continuous
Max Input Voltage
± 20VDC continuous
Agency Approvals
UL, CUL Class I Div II, CE, FCC Class A
Accuracy
Note: Accuracy is dependent on the filter frequency selection,
range selection, data format, and input noise.
Voltage Typ
±0.03% of full scale typical @ 25°C.
Voltage Max
±0.05% of full scale Maximum @ 0 to 60°C.
Current Typ
±0.05% of full scale typical @ 25°C
Current Max
±0.10% of full scale maximum @ 0 to 60°C
Miscellaneous
Display format
12 bit integer, 16 bit integer, 15 bit signed integer,
10000 count DVM