Installation instructions – Spectrum Controls 140 ACI 052 00sc User Manual
Page 24
![background image](/manuals/742159/24/background.png)
Selecting Filter Frequencies: Register 1
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
Default=0x2000 (0x2924 for 140 ACI 050sc)
NU NU
Filter Frequency Group 1
Selecting Filter Frequencies: Register 2
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
Default=0x2A92
NU
NU
NU
NU
Filter Frequency Group 2
Filter Frequency Group 3
Filter Frequency Group 4
Range Selection Bit Pattern:
Filter for Group 1
Filter for Group 2
Reg 1 Bit 3 Bit 4
Description
Reg 2 Bit 15 Bit 16
Description
0
0
10 Hz
0
0
10 Hz
0
1
50 Hz
0
1
50 Hz
*1
0
60 Hz
*1
0
60 Hz
1
1
1000 Hz
1
1
1000 Hz
Filter for Group 3
Filter for Group 4
Reg 2 Bit 12 Bit 13
Description
Reg 2 Bit 9 Bit 10
Description
0
0
10 Hz
0
0
10 Hz
0
1
50 Hz
0
1
50 Hz
*1
0
60 Hz
*1
0
60 Hz
1
1
1000 Hz
1
1
1000 Hz
* The default filter frequency is 60 Hz.
18
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 ACI 052 00sc