Spectrum Controls 140 ACI 052 00sc User Manual

Page 15

background image

Once at power up only

Every 1 min

Every 10 min

[default]

Every 30 min

Selecting an autocalibration schedule rate is an exercise in tradeoffs.

Performing autocalibration more frequently may result in greater

accuracy due to variations caused by environmental factors such as

temperature. This accuracy has a cost in the burden imposed by

performing the calibration. The calibration time is a function of the

filter frequency. Calibration times are listed below. The system

cannot update the channel data while performing calibration. In

addition, if multiple filter frequencies are selected, calibrations for

each frequency and the execution time is cumulative. The worst

case calibration time is when all filter frequencies are enabled (10,

50, 60 and 1000 Hz). The time is then the total for all four times

listed below. Also, note that the channel enables have no effect on

the auto calibration feature. If a filter frequency is enabled via the

zoom screens, then the autocalibration is performed for the frequency.

10 Hz

1,420 msec

50 Hz

397 msec

60 Hz

260 msec

1000 Hz

45 msec

Filter Frequency Selection: The Analog-to-Digital Conversion

performs a filter function on the input signal. One of the following

filter frequencies may be selected for each of the four groups of

eight channels:

Filter:

10 Hz

50 Hz

60 Hz

[default]

1000 Hz

Input data format: One of the following data formats may be selected

for each of the four groups of eight channels:

Format:

16-bit Format

Voltmeter

[default]

12-bit Format

15-bit plus sign Format

9

Installation Instructions

32-Channel Analog Input Module