Installation instructions – Spectrum Controls 140 ACI 052 00sc User Manual
Page 35
![background image](/manuals/742159/35/background.png)
4x Group Select: Bits 13, 14, 15, 16
These four bits are used to select a desired group of channels when the
Auto Sequence mode is not used. The group selection is used when
autosequence is disabled to allow ladder to control which group of the
modules input data, status data, and time stamp data is being read from
the module. The channel Status Mode disables the normal data input
mode and reports the status on the selected group of eight channels.
The channel status bits echo back the selected input range data format
and error status. See description under Status Mode operation.
Date and Channel Status:
Bit 13 Bit 14 Bit 15 Bit 16
Group
0
0
0
0
Channels 1-8
0
0
0
1
Channels 9-16
0
0
1
0
Channels 17-24
0
0
1
1
Channels 25-32
Time Stamp Alarms:
Bit 13 Bit 14 Bit 15 Bit 16
0
0
0
0
Channels 1-2
0
0
0
1
Channels 3-4
0
0
1
0
Channels 5-6
0
0
1
1
Channels 7-8
0
1
0
0
Channels 9-10
0
1
0
1
Channels 11-12
0
1
1
0
Channels 13-14
0
1
1
1
Channels 15-16
1
0
0
0
Channels 17-18
1
0
0
1
Channels 19-20
1
0
1
0
Channels 21-22
1
0
1
1
Channels 23-24
1
1
0
0
Channels 25-26
1
1
0
1
Channels 27-28
1
1
1
0
Channels 29-30
1
1
1
1
Channels 31-32
29
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 ACI 052 00sc