Selecting the Calibration Rate: Register 3
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
Default=0x8205
Time Stamp/Alarm Mode Disable
Time Stamp/Alarm Trigger Mode
Concept Configuration Flag
(Must always be set to 1).
Bit 14 Timestamp Disable:
Bit 13 Timestamp Trigger:
0
Timestamp Alarm Mode Enabeld
*0
Scroll (Store most recent event)
*1
Timestamp Alarm Mode Disabled
1
Latch (Save first event only)
*The default for the timestamp mode is disable = TRUE.
Setting the Alarm Limits: Registers 4-19
The default for the timestamp trigger is scroll (trigger on all events to save most
recent). The Concept Configuration Flag must be set to a 1 when using
Concept software. Registers 4-19 are used to set alarm limits. Each alarm is
defined with a high and low setpoint. Each limit applies to four channels.
☞ Note: The Concept time stamp alarm values apply to groups of four input channels. Modsoft
zoom screens allow for alarm values to be set for groups of two input channels.
The data format for the alarm must match the format for that channels group
as assigned in the first zoom screen. For example, if group 1 configured as a
-10V to +10V range and DVM format, a low of -5000 and a high of 5000 will
trigger alarms at voltages less than or equal to -5V and voltages above +5V
respectively.
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 ACI 052 00sc