Chapter 3
MODULE SETUP FOR CONCEPT
3.1
General Information
Six steps must be performed in order to fully configure the Quantum system
in preparation for using the ACI 052 00sc:
Step 1: Concept programming software (Version 2.1 or newer) must be
updated so that the 140 ACI 052 00sc is recognized in the software
(see Section 3.2).
Step 2: Select the appropriate slot location using the Concept I/O map editor.
Choose the first 3x and 4x level registers to be used in the system
for the modules data, configuration and status information (see
Section 3.3).
Step 3: Parameters for the module must be set to match application
requirements (see Section 3.4).
Step 4: The 4x configuration register must be set to meet application
requirements (see Section 4.1).
Step 5: Module status information is available to you. The various options
must be understood and chosen to meet your application requirements
(see Section 4.2 and Section 4.3).
Step 6: Ladder rungs must be written to demultiplex the incoming 8 data
registers to 32 user selected data registers (see Section 6.3).
13
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 ACI 052 00sc