The register data formats are discussed in the following section.

4x

Configuration Word

3x + 0

Data Input Word 1

4x+1

*Time of Day Clock Control Word

3x + 1

Data Input Word 2

4x+2

Day of Week (Sun+1 Mon+2 etc.)

3x + 2

Data Input Word 3

4x+3

Month (1-12)

3x + 3

Data Input Word 4

4x+4

Day of Month (1-31)

3x + 4

Data Input Word 5

4x+5

Year (00-99)

3x + 5

Data Input Word 6

4x+6

Hour (00-23)

3x + 6

Data Input Word 7

4x+7

Min (00-59)

3x + 7

Data Input Word 8

4x+8

Sec (00-59)

3x + 8

Status Word

*Bit 2 of Time of day clock control word must be set or the PLC will not read clock values

definitions specified. Write either a 4000hex or 6000hex into the first location allocated for

the PLC time of day clock. Refer to the MODSOFT programming manual for more information

on the time of day clock usage.

☞ Note: The PLC time of day clock is read once at power up from registers 4x+1 through 4x+8.

The module’s internal clock chip is synchronized with the PLC clock at this time. After

power up, the module clock is synchronized with the PLC clock at least once a day.

(See Section 4.2 for more details.)

The ACI 052 00sc multiplexes 32 channels of data into four groups of eight

channels. Each group can be selected through the 4x Configuration Word

or can automatically sequence through all four groups channels.

Group 1

Chn 1-8

3x + 0

Data Input Word 1

3x + 1

Data Input Word 2

Group 2

Chn 9-16

3x + 2

Data Input Word 3

3x + 3

Data Input Word 4

Group 3

Chn 17-24

3x + 4

Data Input Word 5

3x + 5

Data Input Word 6

Group 4

Chn 25-32

3x + 6

Data Input Word 7

3x + 7

Data Input Word 8

15

Installation Instructions

32-Channel Analog Input Module

Quantum Series 140 ACI 052 00sc