6.6

Range and Data Format Selection

Each of the module’s input ranges can be viewed in one of the four data

in formats below. The table shows the minimum and maximum values

are equal to the under range and over range trip points.

Format:

Range:

Min:

Max:

Signed 15 Bit

-10 to +10V

-32,767

+32,767

Signed 15 Bit

0 to +10V

0

+32,767

Signed 15 Bit

+1 to +5V

0

+32,767

Signed 15 Bit

+0 to +5V

0

+32,767

Signed 15 Bit

+0 to +20mA

0

+32,767

Signed 15 Bit

+4 to +20mA

0

+32,767

Unsigned 16 Bit

-10 to +10V

0

+65,535

Unsigned 16 Bit

0 to +10V

0

+65,535

Unsigned 16 Bit

+1 to +5V

0

+65,535

Unsigned 16 Bit

+0 to +5V

0

+65,535

Unsigned 16 Bit

+0 to +20mA

0

+65,535

Unsigned 16 Bit

+4 to +20mA

0

+65,535

Unsigned 12 Bit

-10 to +10V

0

+4,095

Unsigned 12 Bit

0 to +10V

0

+4,095

Unsigned 12 Bit

+1 to +5V

0

+4,095

Unsigned 12 Bit

+0 to +5V

0

+4,095

Unsigned 12 Bit

+0 to +20mA

0

+4,095

Unsigned 12 Bit

+4 to +20mA

0

+4,095

10,000 Count DVM

-10 to +10V

-10,000

+10,000

10,000 Count DVM

0 to +10V

0

+10,000

10,000 Count DVM

+1 to +5 V

+1,000

+5,000

10,000 Count DVM

+0 to +5V

0

+5,000

10,000 Count DVM

+0 to +20mA

0

+2,000

10,000 Count DVM

+4 to +20mA

+400

+2,000

48

Installation Instructions

32-Channel Analog Input Module

Quantum 140 ACI 052 00sc