6 range and data format selection, Installation instructions – Spectrum Controls 140 ACI 052 00sc User Manual
Page 54
![background image](/manuals/742159/54/background.png)
6.6
Range and Data Format Selection
Each of the modules input ranges can be viewed in one of the four data
in formats below. The table shows the minimum and maximum values
are equal to the under range and over range trip points.
Format:
Range:
Min:
Max:
Signed 15 Bit
-10 to +10V
-32,767
+32,767
Signed 15 Bit
0 to +10V
0
+32,767
Signed 15 Bit
+1 to +5V
0
+32,767
Signed 15 Bit
+0 to +5V
0
+32,767
Signed 15 Bit
+0 to +20mA
0
+32,767
Signed 15 Bit
+4 to +20mA
0
+32,767
Unsigned 16 Bit
-10 to +10V
0
+65,535
Unsigned 16 Bit
0 to +10V
0
+65,535
Unsigned 16 Bit
+1 to +5V
0
+65,535
Unsigned 16 Bit
+0 to +5V
0
+65,535
Unsigned 16 Bit
+0 to +20mA
0
+65,535
Unsigned 16 Bit
+4 to +20mA
0
+65,535
Unsigned 12 Bit
-10 to +10V
0
+4,095
Unsigned 12 Bit
0 to +10V
0
+4,095
Unsigned 12 Bit
+1 to +5V
0
+4,095
Unsigned 12 Bit
+0 to +5V
0
+4,095
Unsigned 12 Bit
+0 to +20mA
0
+4,095
Unsigned 12 Bit
+4 to +20mA
0
+4,095
10,000 Count DVM
-10 to +10V
-10,000
+10,000
10,000 Count DVM
0 to +10V
0
+10,000
10,000 Count DVM
+1 to +5 V
+1,000
+5,000
10,000 Count DVM
+0 to +5V
0
+5,000
10,000 Count DVM
+0 to +20mA
0
+2,000
10,000 Count DVM
+4 to +20mA
+400
+2,000
48
Installation Instructions
32-Channel Analog Input Module
Quantum 140 ACI 052 00sc