Spectrum Controls 140 ACI 052 00sc User Manual
Page 22
![background image](/manuals/742159/22/background.png)
3.4
Concept I/O Map Module Parameters:
Concept programming software does not implement zoom screens for
ModConnect partner modules and allows only direct editing of the I/O
configuration parameters using 16 bit hex values.
From the Concept main screen, highlight the configure pull-down menu
and choose I/O Map. In the I/O Map screen insert the number for the
correct drop and choose edit. Select the Spectrum Controls catalog
number that you wish to use from the list presented. When the screen appears,
representing the Spectrum module you have selected, highlight the parameters
button. You must insert Hex values for registers #1, 2 and 3 to fully configure
the module. The format that will instruct you how to create the I/O map
parameters is listed below. For each of the parameters listed below we have
provided a detailed explanation in Chapter 2. Please refer to detailed
functional descriptions in the MODSOFT zoom screen discussions (Section
2.4). You must go through each of the options below to establish the correct
pattern for each of these three registers. Once you have the bit pattern, then
you can convert each to a four-digit Hex value that is used in the parameters
screen.
16
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 ACI 052 00sc