Spectrum Controls 140 ACI 052 00sc User Manual
Page 53
![background image](/manuals/742159/53/background.png)
Filter
-3db
1 channel
32 channel
Frequency
Frequency
Update Time
Update time
10 Hz
2.62 Hz
308 ms
9.9 sec
50 Hz
13.1 Hz
68 ms
2.2 sec
60 Hz
15.7 Hz
58 ms
1.9 sec
1K Hz
262 Hz
12 ms
384 ms
☞ Note: Channel update time is the time required for the module to acquire an input sign and
update the modules data registers. The scan rate of the Quantum system will vary with
application ladder and system configuration.
☞ Note: Periodic system calibration will also effect channel update times for one scan cycle.
6.5
System Resolution and Accuracy
The system resolution listed below is the smallest input signal change that the
ADC can detect. The resolution level is affected by the filter frequency selected.
Filter
ADC
Voltage
Current
Frequency
Resolution
Resolution
Resolution
10 Hz
22.5 Bits
3 µV
3 NA
50 Hz
20 Bits
19 µV
19 NA
60 Hz
20 Bits
19 µV
19 NA
1K Hz
10.5 Bits
14 mV
14 µA
The resolution levels for the voltage mode and current mode apply to the full scale
input ranges.
System accuracy is the total error between an actual input signal level and the
module output data value. System accuracy is effected by external wiring, signal
noise, filter frequency, calibration, temperature, and output data formats. The table
below lists that system accuracy verses temperature.
Temp
Voltage Mode
Current Mode
25°C Typical
±0.03% ±6 mV
±0.05% ±10µA
60°C Max
±0.5% ±10mV
±010% ± 20µA
☞ Note: Accuracy calculations are based on the full scale current and voltage input range.
These are 0 to 20 mA and ±10V respectively.
47
Installation Instructions
32-Channel Analog Input Module
Quantum 140 ACI 052 00sc