Filter

-3db

1 channel

32 channel

Frequency

Frequency

Update Time

Update time

10 Hz

2.62 Hz

308 ms

9.9 sec

50 Hz

13.1 Hz

68 ms

2.2 sec

60 Hz

15.7 Hz

58 ms

1.9 sec

1K Hz

262 Hz

12 ms

384 ms

☞ Note: Channel update time is the time required for the module to acquire an input sign and

update the module’s data registers. The scan rate of the Quantum system will vary with

application ladder and system configuration.

☞ Note: Periodic system calibration will also effect channel update times for one scan cycle.

6.5

System Resolution and Accuracy

The system resolution listed below is the smallest input signal change that the

ADC can detect. The resolution level is affected by the filter frequency selected.

Filter

ADC

Voltage

Current

Frequency

Resolution

Resolution

Resolution

10 Hz

22.5 Bits

3 µV

3 NA

50 Hz

20 Bits

19 µV

19 NA

60 Hz

20 Bits

19 µV

19 NA

1K Hz

10.5 Bits

14 mV

14 µA

The resolution levels for the voltage mode and current mode apply to the full scale

input ranges.
System accuracy is the total error between an actual input signal level and the

module output data value. System accuracy is effected by external wiring, signal

noise, filter frequency, calibration, temperature, and output data formats. The table

below lists that system accuracy verses temperature.

Temp

Voltage Mode

Current Mode

25°C Typical

±0.03% ±6 mV

±0.05% ±10µA

60°C Max

±0.5% ±10mV

±010% ± 20µA

☞ Note: Accuracy calculations are based on the full scale current and voltage input range.

These are 0 to 20 mA and ±10V respectively.

47

Installation Instructions

32-Channel Analog Input Module

Quantum 140 ACI 052 00sc