Spectrum Controls 1746sc-NI8u User Manual
Page 94

82
SLC 500
™
Universal Analog Input Module
Thermocouple C Type, Example Variations
-0.5
-0.4
-0.3
-0.2
-0.1
0
0.1
0.2
0.3
0.4
0.5
0
463
926
1389
1852
2315
Degrees C TC Input
Degrees C Variation
Ch 2 Delta, 25C
Ch 2 Delta, 0C
CH 2 Delta, 60C
RTD and Resistance
The following table provides the maximum error for each RTD and
resistance type when the 10 Hz, 50 Hz, and 60 Hz filters are used and the
module is operating at 25°C and was calibrated at 25°C. Errors due to
lead wire resistance mismatches are not included.
Input
Max. Error
Type
25°C
100
Ω
Pt 385
±1.0°C
200
Ω
Pt 385
±0.7°C
500
Ω
Pt 385
±0.6°C
1000
Ω
Pt 385
±0.5°C
100
Ω
Pt 3916
±0.9°C
200
Ω
Pt 3916
±0.6°C
500
Ω
Pt 3916
±0.5°C
1000
Ω
Pt 3916
±0.4°C
10
Ω
Cu 426
±3.0°C
120
Ω
Ni 618
±0.4°C
120
Ω
Ni 672
±0.4°C
3000
Ω
Resistance
±2.0
Ω