64

SLC 500

Universal Analog Input Module

bit (bits 12-15 of the channel status word). Channel fault bits and LEDs
are self-clearing when fault conditions are corrected.

Important: If you clear the channel enable bit, channel status bits are
reset.

LED Indicators

The module has nine LEDs:

• eight channel-status LEDs, numbered to correspond with each channel

• one module-status LED

Module

Channel

Status

Universal Analog

0

1

4

5

INPUT

2

3

6
7

LED for Module Status

LEDs for Channels 0-7

LED Troubleshooting Tables

Table 6.1

Module-status LED

If Module

Status LED is:

Then:

Take this Corrective Action:

On

The module is OK.

No action required.

Off

The module is turned off,

Cycle power. If the condition persists,

or it detected a module

call your local distributor or Spectrum

fault.

Controls for assistance.

Table 6.2

Module-status and Channel-status LED

If Module
Status

And Channel

Then:

Take this Corrective Action:

LED is:

Status LED is:

On

The channel

No action required.

is enabled.

Blinking

The module

Examine error bits in status word

detected:

if bit 12=1, the input has an open circuit

On

open-circuit condition

if bit 13=1, the input value is under range

under-range condition

if bit 14=1, the input value is over range

over-range condition

if bit 15=1, the channel has a diagnostic

channel error

or channel error

Off

The module is in

No action is required.

power up, or the