Led indicators – Spectrum Controls 1746sc-NI8u User Manual
Page 76
64
SLC 500
™
Universal Analog Input Module
bit (bits 12-15 of the channel status word). Channel fault bits and LEDs
are self-clearing when fault conditions are corrected.
Important: If you clear the channel enable bit, channel status bits are
reset.
LED Indicators
The module has nine LEDs:
• eight channel-status LEDs, numbered to correspond with each channel
• one module-status LED
Module
Channel
Status
Universal Analog
0
1
4
5
INPUT
2
3
6
7
LED for Module Status
LEDs for Channels 0-7
LED Troubleshooting Tables
Table 6.1
Module-status LED
If Module
Status LED is:
Then:
Take this Corrective Action:
On
The module is OK.
No action required.
Off
The module is turned off,
Cycle power. If the condition persists,
or it detected a module
call your local distributor or Spectrum
fault.
Controls for assistance.
Table 6.2
Module-status and Channel-status LED
If Module
Status
And Channel
Then:
Take this Corrective Action:
LED is:
Status LED is:
On
The channel
No action required.
is enabled.
Blinking
The module
Examine error bits in status word
detected:
if bit 12=1, the input has an open circuit
On
open-circuit condition
if bit 13=1, the input value is under range
under-range condition
if bit 14=1, the input value is over range
over-range condition
if bit 15=1, the channel has a diagnostic
channel error
or channel error
Off
The module is in
No action is required.
power up, or the
channel is disabled.