Part x. troubleshooting – Austin Hughes IGM-03 User Manual
Page 76

www.austin-hughes.com
UM-IGM-03-Q314V1
P.71
Part X. Troubleshooting
3. How to move out a slave EC Box ( without a replacement ) ?
Step 1 -
Prepare an appropriate length Cat. 5 / 6 cable
Step 2 -
Disable alarm email in < Alarm > page
Step 3 -
Use the Cat. 5 / 6 cable to bridge over the removed slave EC Box to minimize log / data loss
Step 4 -
Power off and remove the slave EC Box from connection
Step 5 -
Reconfigure and reset the level for the affected slave EC Box ( es ) which next to the removed
slave EC Box
Step 6 -
Disable the removed slave EC Box in < Setup > page
Step 7 -
Enable the EC Box ( es ) in < Setup > page based on the new level setting in Step 5
Step 8 -
Click “ Apply “ to save the setting change
Step 9 -
Enable alarm email in < Alarm > page
Ignore step 1, 3, 5 and 7 if the removed slave EC Box is in the last level
4. How to add an extra slave EC Box to an existing Master IP group ?
Step 1 -
Prepare a new slave EC Box and set the slave EC Box level accordingly
( Please refer to user manual < 1.5 > for details )
Step 2 -
Prepare an appropriate length Cat. 5 / 6 cable
Step 3 -
Disable alarm email in < Alarm > page
Step 4 -
Install, connect and power on the new slave EC Box
Step 5 -
Reconfigure and reset the level for the affected slave EC Box ( es ) which next to the added
slave EC Box
Step 6 -
Enable the added slave EC Box in < Setup > page
Step 7 -
Enable the EC Box ( es ) in < Setup > page based on the new level setting in Step 5
Step 8 -
Click “ Apply “ to save the setting change
Step 9 -
Configure the new slave EC Box in < EC Box Setting > page such as Name, Location
Step 10 -
Enable alarm email in < Alarm > page
Ignore step 3, 5, 7 and 11 if the added slave EC Box is in the last level