1/2 Setpoints

Occ. cool.

Standby cool.

Unocc. cool.

25.5 °C

24.0 °C

22.0 °C

20.5 °C

16.5 °C

26.5 °C

Occ. heat.

Standby heat.

Unocc. heat.

SETPOINT SETTINGS 1/2

SETPOINT PARAMETER DETAILS

Configuration Parameters Default Value

Significance and Adjustments

Unocc. cool.
Default value:

26.5 °C (80 °F)

Unoccupied Cooling

Unoccupied cooling setpoint range: 2.0 to 37.5 °C (54 to 100 °F).

Standby cool.
Default value:

25.5 °C (78 °F)

Standby Cooling

The value of this parameter should be set between occupied and
unoccupied cooling setpoints. Ensure difference between standby
and occupied value can be recovered in a timely fashion when
movement is detected in the zone.

Stand-by cooling setpoint range: 12.0 to 37.5 °C (54 to 100 °F).

Occ. cool.
Default value:

24.0 °C (74 °F)

Occupied Cooling

Cooling setpoint range: 12.0 to 37.5 °C (54 to 100 °F).

Occ. heat.
Default value:

22.0 °C (72 °F)

Occupied Heating

Heating setpoint range: 12.0 to 37.5 °C (54 to 100 °F).

Standby heat.
Default value:

20.5 °C (69 °F)

Standby Heating

The value of this parameter should be set between occupied and
unoccupied heating setpoints. Ensure difference between standby
and occupied value can be recovered in a timely fashion when
movement is detected in the zone.

Stand-by heating setpoint range: 4.5 to 32.0 °C (40 to 90 °F).

Unocc. heat.
Default value:

16.5 °C (62 °F)

Unoccupied Heating

Unoccupied heating setpoint range: 4.5 to 32.0 °C (40 to 90 °F).