beautypg.com

Vt8600 series user interface guide – Viconics VT8600 User Interface Guide User Manual

Page 22

background image

VT8600 Series

User Interface Guide

22

Viconics Technologies Inc.

9245 Langelier Blvd. Saint-Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660

028-0441-00

www.viconics.com

November 2014

© 2

01

4 V

ic

on

ic

s T

ec

hn

ol

og

ie

s. A

ll r

ig

ht

s r

es

er

ve

d

.

5/9 Configuration

Heat stages

Prop. band

2

3.0

Econo. config

Off

ChngOvr Sp

13.0 °C

Cool stages

2

Mech cooling

Off

CONFIGURATION PARAMETERS SCREEN 5/9

PARAMETER DETAILS SCREEN 5/9

Configuration Parameters Default Value

Significance and Adjustments

Prop. band
Default value:

3.0

Proportional Band Setting

Adjusts proportional band used by the Terminal Equipment Controller PI control
loop.

Note: default value of 3.0 gives satisfactory operation in most normal installation
cases. The use of a superior proportional band different than the factory one is
normally warranted in applications where Terminal Equipment Controller location is
problematic and leads to unwanted cycling of the unit. A typical example is a wall
mounted unit where Terminal Equipment Controller is installed between return and
supply air feeds and is directly influenced by the supply air stream of unit.

Value

Effective Proportional Band

Fahrenheit

Celsius

3

3

1.2

4

4

1.7

5

5

2.2

6

6

2.8

7

7

3.3

8

8

3.9

9

9

5.0

10

10

5.6