5/9 Configuration
Heat stages
Prop. band
2
3.0
Econo. config
Off
ChngOvr Sp
13.0 °C
Cool stages
2
Mech cooling
Off
CONFIGURATION PARAMETERS SCREEN 5/9
PARAMETER DETAILS SCREEN 5/9
Configuration Parameters Default Value
Significance and Adjustments
Prop. band
Default value:
3.0
Proportional Band Setting
Adjusts proportional band used by the Terminal Equipment Controller PI control
loop.
Note: default value of 3.0 gives satisfactory operation in most normal installation
cases. The use of a superior proportional band different than the factory one is
normally warranted in applications where Terminal Equipment Controller location is
problematic and leads to unwanted cycling of the unit. A typical example is a wall
mounted unit where Terminal Equipment Controller is installed between return and
supply air feeds and is directly influenced by the supply air stream of unit.
Value
Effective Proportional Band
Fahrenheit
Celsius
3
3
1.2
4
4
1.7
5
5
2.2
6
6
2.8
7
7
3.3
8
8
3.9
9
9
5.0
10
10
5.6