Vt8600 series, User interface guide, Parameter details screen 1/9 – Viconics VT8600 User Interface Guide User Manual
Page 15: Configuration parameters screen 1/9
![background image](/manuals/715518/15/background.png)
VT8600 Series
15
User Interface Guide
© 2
01
4 V
ic
on
ic
s T
ec
hn
ol
og
ie
s. A
ll r
ig
ht
s r
es
er
ve
d
.
Viconics Technologies Inc.
9245 Langelier Blvd. Saint-Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660
028-0441-00
www.viconics.com
November 2014
PARAMETER DETAILS SCREEN 1/9
Configuration Parameters Default Value
Significance and Adjustments
UI 16
Universal input no.1 configuration
Default value:
None
Universal Input No. 1
None: No function will be associated with the input. Input can be
used for remote network monitoring.
Rem NSB: remote NSB timer clock input. The scheduling will now
be set as per the binary input. It provides low cost setback opera-
tion via a dry contact
• Contact opened = Occupied
• Contact closed = Unoccupied
Window: Forces the system to disable any current heating or
cooling action by the Terminal Equipment Controller. The mode
stays the same and the current setpoints are the same occupied
setpoints. Only the outputs are disabled. There is a Door/Window
alarm displayed on the Terminal Equipment Controller to indicate
to the local tenant that the door/window needs to be closed for
cooling or heating to resume. Use NC contact.
• Contact opened = System disabled with local Window alarm
• Contact closed = System enabled
Service: a service alarm shows on the Terminal Equipment
Controller LCD screen when input is energized.
Fan lock: a fan lock alarm will be displayed on the Terminal
Equipment Controller LCD screen when the input is not energized.
• Open contact = no airflow
• Closed contacts = airflow present
1/9 Configuration
UI19 config
UI17 config
UI16 config
None
None
None
Occupancy cmd
Loc occ.
Smart recovery
Off
Setpoint func.
Attach Stp
CONFIGURATION PARAMETERS SCREEN 1/9