PARAMETER DETAILS SCREEN 1/9

Configuration Parameters Default Value

Significance and Adjustments

UI 16
Universal input no.1 configuration
Default value:

None

Universal Input No. 1
None
: No function will be associated with the input. Input can be
used for remote network monitoring.
Rem NSB: remote NSB timer clock input. The scheduling will now
be set as per the binary input. It provides low cost setback opera-
tion via a dry contact
• Contact opened = Occupied
• Contact closed = Unoccupied
Window: Forces the system to disable any current heating or
cooling action by the Terminal Equipment Controller. The mode
stays the same and the current setpoints are the same occupied
setpoints. Only the outputs are disabled. There is a Door/Window
alarm displayed on the Terminal Equipment Controller to indicate
to the local tenant that the door/window needs to be closed for
cooling or heating to resume. Use NC contact.
• Contact opened = System disabled with local Window alarm
• Contact closed = System enabled
Service: a service alarm shows on the Terminal Equipment
Controller LCD screen when input is energized.
Fan lock: a fan lock alarm will be displayed on the Terminal
Equipment Controller LCD screen when the input is not energized.

• Open contact = no airflow
• Closed contacts = airflow present

1/9 Configuration

UI19 config

UI17 config

UI16 config

None

None

None

Occupancy cmd

Loc occ.

Smart recovery

Off

Setpoint func.

Attach Stp

CONFIGURATION PARAMETERS SCREEN 1/9