PARAMETER DETAILS SCREEN 5/9

Configuration Parameters Default Value

Significance and Adjustments

Heat stages
Number of heating stages.
Applicable to 2 stage models only
Default value:

2 stages

Will revert the operation of 2 stages Terminal Equipment Controller to single
stage operation only when the second heating step is not needed.

1 or 2 stages

Cool stages
Number of cooling stages
Default value:

2 stages

Will revert the operation of 2 stage Terminal Equipment Controller to single
stage operation only when the second cooling step is not needed.
1 or 2 stages

Econo. config
Economizer configuration
Default value:

Off

Controls the activity of the economizer functionality
On Economizer is activated
Off Economizer is deactivated

ChngOvr Sp
Changeover setpoint
Default value:

55 °F (13.0 °C)

In Cooling mode.
The outside air temperature value at which the cooling will be switched over
from mechanical (compressor) to free cooling (economizer)
14 to 70 °F (-10.0 to 21.0 °C)

Mech cooling
Mechanical cooling allowed
Default value:

Off

In Cooling mode.
Allows the operation of the mechanical cooling if the free cooling (economizer)
cannot maintain the cooling setpoint.
Off Typically applies when the MS (mixed air temperature sensor) is installed
after the mechanical cooling refrigeration coils. In this case, mechanical cooling
will never operate at the same time as free cooling.
On Typically applies when the MS (mixed air temperature sensor) is installed
before the mechanical cooling refrigeration coils in the mixing plenum. In this
case, mechanical cooling is allowed when the free cooling (economizer opera-
tion) cannot maintain the cooling setpoint.
Off or On