Schedule menu
8/9 Configuration
User password
Main password
0
0
Calib. temp.
0.0 C
Calib. OS temp. 0.0 C
Enabled
CONFIGURATION PARAMETERS SCREEN 8/9
PARAMETER DETAILS SCREEN 8/9
Configuration Parameters Default Value
Significance and Adjustments
Main password
Default value:
0
Main Password
Installer password. This parameter sets a protective access
password to prevent unauthorized access to configuration menu
parameters.
Default value of 0 does not prompt a password or lock access
configuration menu.
Range: 0 - 9999.
User Password
Default value:
0
User Password
User password. This parameter sets a protective access password
to prevent user unauthorized access to main screen adjustments.
Default value of 0 does not prompt a password.
Range: 0 - 9999.
Schedule menu
Default value:
Enabled
Toggles activation of schedule menu direct access
Enabled The Schedule Menu is directly accessible from the main
screen via a touch in the upper corner (see page 4).
Disabled The Schedule Menu can only be accessed through the
Setup Menu screens
Calib. temp.
Default value:
0.0 °C or °F
Calibration Temperature
Room temperature sensor calibration. Offset can be added or
subtracted to actual displayed room temperature.
Range: ± 2.5 °C, 0.5 °C increments (± 5.0 °F, 1.0 °F
increments).
Calib. OS temp.
Default value:
0.0 °C or °F
Calibration Outside Temperature
Outside air temperature sensor calibration. Offset that can be
added/subtracted to the actual displayed outdoor temperature.
Range: ± 2.5 °C, 0.5 °C increments (± 5.0 °F, 1.0 °F
increments).