BACNET NETWORK SETTINGS

BACnet network set-up screen shows when BACnet is detected in model. Select desired parameter and use up or down arrow to set
parameter to desired value.

1/2 BACnet network

Baud rate

Auto

Network units

SI

Network lang.

English

BACnet status

Offline

COM address

254

254 value sets BACnet

®

network Offline. Choose different
value to activate Online

Imperial or
Metric units

Language setting

Baud rate
settings

Displays BACnet status,
Offline or Online

PARAMETER DETAILS

Configuration Parameters Default Value

Significance and Adjustments

Comm address
Terminal Equipment Controller
networking address
Default value:

254

Range:

0 to 254

Communication Address

For BACnet

®

MS-TP models, the valid range is from 1 to 127.

Default value of 254 disables BACnet

®

communication for the Terminal

Equipment Controller.

Network units
Default value:

Imperial

Measurement Units

(

Imperial): network units shown as Imperial units.

(

SI): network units shown as International Metric units.

Network lang
Default value:

English

Language Settings

Choice of network language/object names transmitted over network.
All available choices: (English, French, Spanish, Russian, Chinese).

Baud rate
Default value:

Auto

Baud Rate

(

Auto): automatically detects BACnet

®

MS/TP baud rate.

Other choices: (115200, 76800, 57600, 38400, 19200, and 9600).