4/9 Configuration

Frost protec.

Heating CPH

Cooling CPH

Off

4

4

BO1 aux config

NO

Anti short cycle

2 min

CONFIGURATION PARAMETERS SCREEN 4/9

PARAMETER DETAILS SCREEN 4/9

Configuration Parameters Default Value

Significance and Adjustments

Cooling CPH
Cooling stages cycles per hour.
Default value:

4 CPH

Sets the maximum number of cooling stage cycles per hour under
normal control operation. It represents the maximum number of
cycles that the equipment will turned on and off in one hour.
Note that a higher CPH will represent a higher accuracy of control at
the expense of wearing mechanical components faster.
3 or 4 CPH
For multi stage models, cool CPH applies to Y1 & Y2

Heat CPH
Heating stages cycles per hour.
Default value: 4 CPH

Will set the maximum number of heating stage cycles per hour
under normal control operation. It represents the maximum number
of cycles that the equipment will turn ON and OFF in one hour.

Note that a higher CPH will represent a higher accuracy of control at
the expense of wearing mechanical components faster.

3, 4, 5, 6,7 & 8 CPH

For multi stage models, heat cph applies to W1 & W2