beautypg.com

Vt8600 series, User interface guide, Parameter details – Viconics VT8600 User Interface Guide User Manual

Page 11

background image

VT8600 Series

11

User Interface Guide

© 2

01

4 V

ic

on

ic

s T

ec

hn

ol

og

ie

s. A

ll r

ig

ht

s r

es

er

ve

d

.

Viconics Technologies Inc.

9245 Langelier Blvd. Saint-Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660

028-0441-00

www.viconics.com

November 2014

PARAMETER DETAILS

Configuration Parameters Default Value

Significance and Adjustments

ZigBee Pan ID
Personal Area Network
Identification
Default value:

0

Range value:

0 - 1000

ZigBee Pro PAN ID

Links specific Terminal Equipment Controllers to
specific ZigBee

®

Pro coordinators. For every Terminal Equipment

Controller reporting to a coordinator. Ensure set the SAME
channel value both on the coordinator and the Terminal Equipment
Controller(s).

Default value of 0 is NOT a valid PAN ID. The valid range of
available PAN ID is from 1 to 1000.

Range 1 to 500 for centralized networked applications using a
ZigBee

®

Pro Coordinator.

Range 501 to 1000 is for stand-alone applications where each
controller is its own coordinator for stand alone installation of
wireless door and window switches.

ZigBee channel
Channel selection
Default value:

10

Range value:

11 - 25

ZigBee channel
This parameter links specific Terminal Equipment Controllers to
specific ZigBee

®

Pro coordinators. For every Terminal Equipment

Controller reporting to a coordinator, ensure you set the SAME
channel value both on the coordinator and the Terminal Equipment
Controller(s).

Using channels 15 and 25 is recommended.

The default value of 10 is NOT a valid channel. The valid range of
available channel is from 11 to 25.

ZigBee status
Read only

ZigBee status
The following read only messages show in this field:

(Not Det): ZigBee

®

Pro module not detected

(Pwr On): ZigBee

®

Pro module detected but not configured

(No NWK): ZigBee

®

Pro configured but no network joined

(Joined): ZigBee

®

Pro network joined

(Online): Communicating

Note: The following menus shows according to context:

1. If ZigBee Pro card is detected, ZigBee configuration menus automatically show.

2. Bacnet menus show if model supports BACnet.

3. Network choice inside Setup screen does not show if no network is available.