PARAMETER DETAILS SCREEN 1/9
Configuration Parameters Default Value
Significance and Adjustments
UI 17
Universal input no.2 configuration
Default value:
None
Universal Input No. 2
None: No function will be associated with the input. Input can be
used for remote network monitoring.
Door Dry: This configuration is only functional if binary input #1 is
set to Motion NO or Motion NC or an onboard PIR sensor is used.
With this sequence enabled, the occupancy is now dictated through
those 2 inputs. Any motion detected will set the zone to occupied
status. The zone will remain permanently in occupied mode until the
door contact switch opens momentarily. The Terminal Equipment
Controller will then go in stand-by mode. If more movements are
detected, the occupied mode will resume. While the door is opened,
any movements detected by the remote PIR sensor or the onboard
PIR sensor will be ignored. Use a Normally Closed contact switching
device.
• Contact opened = Door opened
• Contact closed = Door closed
Override: temporary occupancy remote override contact.
Filter: a filter alarm shows on the Terminal Equipment Controller
LCD screen when the input is energized.
Service: a service alarm shows on the Terminal Equipment
Controller LCD screen when input is energized.
UI 19
Universal input no.3 configuration
Default value:
None
Universal Input No. 3
None: no function associated with input though input can be used
for remote network monitoring.
CO2: the 0-10VDC input value is used as a 0-2000ppm
CO2 level:
0 VDC = 0ppm
10VDC = 2000ppm
Occupancy cmd
Default value:
Local
Occupancy Command
Loc Occ: occupancy is determined by local sequences.
Occupied: force occupied mode.
Unoccup: force unoccupied mode.
Prog recovery
Progressive recovery enabled
Default value:
Off
Progressive recovery is automatically disabled if UI 16 and / or
UI 17 are configured remote NSB
Off = no progressive recovery
The occupied schedule time is the time at which the system will
restart.
On = progressive recovery active.
The occupied schedule time is the time at which the desired
occupied temperature will be attained. The controller will
automatically optimize the equipment start time.
In any case, the latest a system will restart is 10 minutes prior to the
occupied period time.
Setpoint func.
Local setpoint settings
Default value =
Dual Stp
Set the local setpoint interface for the user
Dual Stp (Dual Occupied Setpoints Adjustment)
Attach Stp (Single Occupied Setpoint Adjustment)