PARAMETER DETAILS SCREEN 7/9

Configuration Parameters Default Value

Significance and Adjustments

Min CO2
Minimum CO2 Level
Default value:

800 ppm

Minimum CO2 Level required. Effective only in Occupied mode
(Fan is ON). This value is used to determine the fresh air damper
position based on the Min/Max CO2 and Min/Max Pos values
set. See Fresh Air Damper Position section for more details.
0 to 2000 ppm, 10 or 100 increments

Max CO2
Maximum CO2 Level
Default value:

1200 ppm

Maximum CO2 Level allowed. Effective only in Occupied mode
(Fan is ON). This value is used to determine the fresh air damper
position based on the Min/Max CO2 and Min/Max Pos values
set. See Fresh Air Damper Position section for more details.
0 to 2000 ppm, 10 or 100 increments