PARAMETER DETAILS SCREEN 2/9

Configuration Parameters Default Value

Significance and Adjustments

Standby mode
Default value:

Abs

Standby Mode
Choose which standby setpoints are used for control.
Abs: absolute Standby entered values are used for standby mode.
Offset: relative Occupied setpoints +/- Standby diff. used for standby
mode.

Standby diff.
Default value:

2 °C ( 3 °F )

Standby Difference
When Standby mode is Relative, standby setpoints are calculated as:
Standby cool = Cool setpoint + Standby diff.
Standby heat = Heat setpoint - Standby diff.
Adjustable from 0.5 a 2.5 °C ( 1 - 5 °F )

Power-up delay
Default value:

10 seconds

On initial power up of the Terminal Equipment Controller (each time 24
Vac power supply is removed & re-applied) there is a delay before any
operation is authorized (fan, cooling or heating). This can be used to
sequence start up multiple units / Terminal Equipment Controller in one
location.
10 to 120 seconds