beautypg.com

Vt8600 series, User interface guide, Wireless ecosystem – Viconics VT8600 User Interface Guide User Manual

Page 7: Parameter details

background image

VT8600 Series

7

User Interface Guide

© 2

01

4 V

ic

on

ic

s T

ec

hn

ol

og

ie

s. A

ll r

ig

ht

s r

es

er

ve

d

.

Viconics Technologies Inc.

9245 Langelier Blvd. Saint-Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660

028-0441-00

www.viconics.com

November 2014

WIRELESS ECOSYSTEM

When wireless sensors are set up to communicate with a room controller, the functioning of each such sensor is described in a separate
Zone screen, up to a maximum of 10 Zones. Select the appropriate type of sensor based on the required functioning using the up and
down arrow keys.

Set function to

Status

1/10 Zone

Battery

No

Paired

0x0000

IEEE address

None

Closed

Normal

Permit join

On

Set function to

Status

10/10 Zone

Battery

No

Paired

0x0000

IEEE address

None

Closed

Normal

PARAMETER DETAILS

Configuration Parameters Default Value

Significance and Adjustments

Set function to
Describe function of specified wireless sensor
Default value: None

None: No sensor function configured for this zone
Door: Sensor is a door contact switch
Window: Sensor is a window contact switch
Motion: Sensor is a motion sensor
Status: Updates the BACnet status of the sensor, but no action is
taken by the internal logic of the controller.
Remove: Selecting this function clears the zone of the settings for
the attached sensor. However, the sensor will automatically try to
reconnect with the room controller unless it is manually reset as
well.

Status
Current status of information received from the sensor
Read only

Close: Sensor in closed state (door/window only)
Open: Sensor in opened state (door/window only)
No motion: Sensor detects no motion (motion sensor only)
Motion: Sensor detects motion (motion sensor only)
None: No status information received from sensor.

Battery
Current status of sensor battery, if any.
Read only

Low: Battery power level is low, replacement or recharge will be
needed soon
Normal: Battery power level is in the normal range, replacement or
recharge is not currently needed.
None: Sensor does not use a battery

Paired
Sensor pairing state
Read only

No: Sensor is not paired with the room controller
Yes: Sensor is paired with the room controller
Invalid: Sensor cannot be paired.

Identical to ZigBee
settings display
parameter, see
page 12