2/9 Configuration

Fan delay

On

Off

Standy mode

Abs

Standby diff.

2.0 °C

Fan cont. heat

Power-up delay

10 Sec.

CONFIGURATION PARAMETERS SCREEN 2/9

PARAMETER DETAILS SCREEN 2/9

Configuration Parameters Default Value

Significance and Adjustments

Fan cont. heat
Fan control
Default value:

On

Fan control in heating mode.
When selecting

On; the Terminal Equipment Controller in all cases

will always control the fan (terminal G).
Valid for

On or Auto fan mode

When selecting

Off; the fan (terminal G), when heating stages

(terminals W1 & W2) are solicited, will not be energized. The fan in
this case will be controlled by the equipment fan limit control.
Valid only for

Auto fan mode. On fan mode will leave the fan

always on.
ON OR OFF
For multi stage models, fan control applies to W1 & W2

Fan delay
Default value:

Off

Fan delay extends fan operation by 60 seconds after the call for
heating or cooling ends.
Valid only for

Auto fan mode. On fan mode will leave the fan

always on.
Off or On