Warning – SUUNTO VYTEC User Manual
Page 30

28
WARNING!
YOUR ACTUAL ASCENT TIME MAY BE LONGER THAN DIS-
PLAYED BY THE INSTRUMENT! The ascent time will increase if you:
remain at depth
ascend slower than 10 m/min [33 ft/min] or
make your decompression stop deeper than at the ceiling.
These factors will also increase the amount of air required to reach
the surface.
CEILING, CEILING ZONE, FLOOR AND
DECOMPRESSION RANGE
When in decompression, it is important that you understand the mean-
ing of ceiling, floor, and decompression range (Fig. 3.20.):
The ceiling is the shallowest depth to which you should ascend
when in decompression. At this depth, or below, you must
perform all stops.
The ceiling zone is the optimum decompression stop zone. It is
the zone between the minimum ceiling and 1.8 m [6 ft] below
the minimum ceiling.
The floor is the deepest depth at which the decompression stop
time will not increase. Decompression will start when you pass
this depth during your ascent.
The decompression range is the depth range between the
ceiling and floor. Within this range, decompression takes place.
However, it is important to remember that the decompression
will be very slow at, or close to, the floor.
The depth of the ceiling and floor will depend on your dive profile. The
ceiling depth will be fairly shallow when you enter the decompression
mode, but if you remain at depth, it will move downward and the ascent
time will increase. Likewise, the floor and ceiling may change upwards
while you are decompressing.
When conditions are rough, it may be difficult to maintain a constant
depth near the surface. In this case it will be more manageable to main-
tain an additional distance below the ceiling, to make sure that the
waves do not lift you above the ceiling. Suunto recommends that de-
compression takes place deeper than 4 m [13 ft], even if the indicated
ceiling is shallower.