Vent Temperature Limit Switch (High Efficiency Models Only)

The vent temperature limit switch is located on the discharge of the combustion air

blower (venter) and its purpose is to prevent the vent gas temperature from exceed-

ing a temperature that will harm the PVC vent pipe. If the vent temperature limit

switch is activated, the cause must be determined and corrected before the heater

is placed back into operation. Activation of the manually reset vent temperature limit

switch could be caused by one or more of the following:

Manifold gas pressure too high

The heat content of the fuel being burned is too high

Reduced circulating airflow due to dirty and/or plugged air moving components

Excess dirt on the heat exchangers

Failed heat exchanger(s)

After the cause is determined and corrected, depress the red button on the switch to

reset it.

Vent Temperature

Limit Switch

IMPORTANT: When using a multimeter to troubleshoot the 24 volt circuit, place the

meter’s test leads into the 5 or 9 pin connectors located on the ignition control. Do not

remove connectors or terminals from the electrical components. Doing so can result

in misinterpreted readings due to the ignition control board’s fault mode monitoring

circuits.

LED Flash Codes for

DSI Control Module

Flash Code Description

Fast Flash Normal operation

Steady OFF No power, blown fuse, or defective board

1

Low pressure switch stuck open

2

Low pressure switch stuck closed

3

High pressure switch stuck open

4

High pressure switch stuck closed

5

Limit switch open

6

Ignition lockout (failed ignition)

7

Too many (5) limit switch losses

8

Too many (5) flame losses

9

Too many (3) high pressure switch losses during one call for heat

DSI Control Module

P/N 272626

LED Light

Only replaceable part is a Type ATC or ATO

3 amp fuse (color code violet), P/N 201685.