beautypg.com

Reznor YDSA Operation Manual User Manual

Page 23

background image

Form O-Y P/N 273647R1, Page 23

change the filter drier any time the circuit is opened.

It is recommended to use a tubing cutter when cutting out a filter drier as the

desiccant absorbs and holds moisture better when it is cool. Heat from a torch may

cause moisture to leave the filter and be absorbed in the oil. Be careful to keep

dirt, filings, and other contaminants out of the system.
Continue to

Step 5.

IF the oil measured in Step 2 was significantly less than shown in the table above

or the test for acid in

Step 2 did indicate compressor burnout, do the following:

a) Install a liquid line filter drier. If there is acid, install an acid removing filter

drier. Size the acid-removing filter drier at least one capacity size larger than

normally required for the circuit.

b) Install a temporary filter drier in the suction line. When there is acid, a 100%

activated alumina suction filter drier is recommended. The suction line drier

should be sized properly for the circuit and have a service access fitting to

monitor pressure drop across the drier. (NOTE: Suction line filter drier must be

removed after 72 hours of operation.)

Step 12 includes the remaining procedures required for cleanup of a burnout.

Continue to Step 5.

Step 5. Braze on Suction and Discharge Lines

CAUTION: Do not leave system open to the atmosphere any longer

than minimum required for installation. POE oil in the compressors is

extremely susceptible to moisture absorption. Always keep ends of

tubing sealed during installation. See Hazard Levels, page 2.

Brazing materials must be able to withstand the high pressure of R-410A

refrigerant. A high temperature, silver phosphate type brazing with 5% or greater

alloy is recommended.
To prevent oxidation, purge tubing with 2-3 psig of regulated dry nitrogen while it

is being brazed. Open the service valve as needed to release the nitrogen. Do not

allow moisture to enter the system.
The installer is responsible for brazing and for complying with appropriate standard

refrigerant piping procedures.

CAUTION: All brazing should be done using a 2-3 psig dry nitrogen

purge flowing through the pipe being brazed.

CAUTION: When brazing, protect all painted surfaces and components

from excessive heat. Wet wrap all valves but do not allow moisture to

enter the tubing. See Hazard Levels, page 2.

Step 6. Check System for Leaks

After installation is complete, pressurize the circuit with helium or dry nitrogen to

approximately 150 psi (maximum pressure is 450 psi). Check for leaks using soap

bubbles or other leak-detecting methods.

Step 7. Evacuate the Circuit

Evacuate one circuit at a time. Use a vacuum pump and micron gauge. Each

circuit must be evacuated to hold a 500 micron vacuum. Vacuum must be pulled

on both the discharge (high) and suction (low) side. Do the suction side first; and

the compressor discharge side second. To establish that a circuit is leak-free

and moisture-free, a standing vacuum test is recommended. Close off the valve

to the vacuum pump and observe the micron gauge. If the vacuum gauge does

not rise above 500 microns in one minute, the evacuation should be complete.

If the vacuum gauge does rise above 500 microns in one minute, evacuation

is incomplete or the circuit has a leak. Repeat as needed until evacuation is

complete. The evacuation process must be done on each circuit.
NOTE: Evacuation will not remove moisture from POE oil. Moisture must be

prevented from getting in the oil.

Continue and/or repeat

Steps 6 and 7 until evacuation is complete.

3.7 Compressor

Operation,

Maintenance,

and

Replacement

(cont'd)

This manual is related to the following products: