1 maintenance schedule, Warning, Monthly – Reznor YDSA Operation Manual User Manual

Page 3: Annually

background image

Form O-Y P/N 273647R1, Page 3

IMPORTANT: Do not release refrigerant to the atmosphere! If

required service procedures include the adding or removing

of refrigerant, the service technician must comply with all

federal, state and local laws. The procedures discussed in

this manual should only be performed by a qualified HVAC

technician familiar with R-410A refrigerant.

WARNING

Lock power OFF before performing any maintenance

procedure (except where power is required such as

checking refrigerant pressure and temperature). Lock

disconnect switch in OFF position. If the system has a gas

heat section, when you turn off the power supply, turn off

the gas. See Hazard Levels on page 2.

2.1 Maintenance

Schedule

Monthly

Inspect all filters; clean or replace as needed. See Paragraph 3.1, page 6.

Inspect the cooling coil condensate drain; clean as needed. For information, see

Paragraph 3.5, page 10.

Annually

All Models - Beginning of the cooling season or more frequently

in year-round cooling climate:

Inspect the wiring for any damaged wire. Replace damaged wiring.

Inspect the cooling coil condensate drain pan. Clean the coil cabinet, clean the

drain pan, and fill the trap.

Inspect/clean condenser fans. See Paragraph 3.4, page 10.

Inspect/clean all coils. See Paragraph 3.5, page 10.

Check refrigerant temperatures and pressures (superheat and subcooling).

These checks are done when the unit is operating. See Paragraph 3.6, page 17.

Check compressor operation. See Paragraph 3.7, page 19.

Systems with the Optional energy recovery wheel: See Paragraph 4.0, page 27.

Inspect the wheel and clean as needed.

Check wheel RPM and drive components.

Check wheel seals.

Systems with the Optional gas heat section (beginning of the heating

season) - See Paragraph 5.0, page 32:

Clean all dirt and grease from the combustion air openings and the venter

assembly.

Check the heat exchanger, burner, and venter for scale, dust, or lint

accumulation. Clean as needed.

Check the gas valves to ensure that gas flow is being shutoff completely.

Systems with the Optional electric heat section (beginning of the

heating season) - See Paragraph 6.0, page 42:

Check wiring connections.

Check the heat section and elements for dust or lint accumulation. Clean as

needed.

If replacement parts are required, use only factory-authorized parts. For