Form O-Y P/N 273647R1, Page 13

Optional Modulating

Reheat (Low Enthalpy

Option RPLE or High

Enthalpy Option

RPHE)

Function: Units equipped with optional reheat have a dedicated refrigerant system

(DH circuit) that precools the incoming air then directly uses the condenser waste

heat to reheat the air after it passes through the DX cooling coil. The reheat system

precooling evaporator coil is upstream of the main evaporator coil and the reheat

condenser coil is downstream. The upstream "precool" coil tempers outside air and

lowers the wet bulb depression of the air entering the main evaporator coil. The heat

removed at the precool coil is rejected to the downstream "reheat" coil.
Operation of the DH circuit is controlled by the digital controller in the electrical

compartment. See

FIGURE 1(shown on page 4) and Figures 13 and 14 (shown on

pages 13 & 14). The digital controller interfaces with the system controller and pro-

vides protection and diagnostics for compressor operation.
Service: See Troubleshooting Chart in Paragraph 7.2 on page 45 for identification of

alarm codes. Use only factory-authorized replacement parts.

FIGURE 12 - Cooling

Circuits - Models

YDHA and YDMA

Sizes 300 and 360

Circuit A

Circuit B

Equilizer Tube

Filter Drier

Evaporator Coil

View from Cooling Cabinet Door

(Evaporator Coil Side)

TXV

Valves

View from Compressor and

Condenser Section

Circuit B

Compressor

(Circuit B)

Circuit B

Condenser Coil

Circuit B

Condenser Coil

Circuit

A

Filter Drier

Compressor

(Circuit A)

Filter Drier

Circuit A

Circuit A

Circuit A

Circuit B

Model YDHA 300 and 360 (Cabinet 3)

Model YDMA 300 and 360 (Cabinet 3)

FIGURE 13 - Optional

DH Circuit (Option

RPLE Low Enthalpy

Reheat Pump or

Option RPHE High

Enthalpy Reheat Pump

Model YDHA 060, 090, 120, and 150 (Cabinet 1)
Model YDMA 060, 090, 120, and 150 (Cabinet 1)
Model YDSA 120 and 150 (Cabinet 2)
Model YDHA 180, 210, and 240 (Cabinet 2)
Model YDMA 180, 210, and 240 (Cabinet 2)

DH

Coil

Condenser Coil

Circuit A

Condenser Coil

Circuit B

View from Compressor and

Condenser Section

Modulating

Compressor

(Optinal DH Circuit)

Solenoid

Valve

View from Cooling Cabinet Door

(Evaporator Coil Side)

Equalizer

Tube

Filter

Drier

TXV Valve

Circuit DH

DH

Coil

This manual is related to the following products: