7 compressor operation, maint, and replacement 19, Danger, Warnings – Reznor YDSA Operation Manual User Manual

Page 19

background image

Form O-Y P/N 273647R1, Page 19

R-410A Refrigerant

R-410A Refrigerant

R-410A Refrigerant

R-410A Refrigerant

R-410A Refrigerant

Pressure Temperature

Pressure Temperature

Pressure Temperature

Pressure Temperature Pressure Temperature

PSI

°F

°C

PSI

°F

°C

PSI

°F

°C

PSI

°F

°C

PSI

°F

°C

1.8

-55 -48.3

49.5

1

-17.2

77.0

19

-7.2

112.2

37

2.8

218.2

75

23.9

4.3

-50 -45.6

50.9

2

-16.7

78.7

20

-6.7

114.4

38

3.3

235.9

80

26.7

7.0

-45 -42.8

52.2

3

-16.1

80.5

21

-6.1

116.7

39

3.9

254.6

85

29.4

10.1

-40 -40.0

53.6

4

-15.6

82.3

22

-5.6

118.9

40

4.4

274.3

90

32.2

13.5

-35 -37.2

55.0

5

-15.0

84.1

23

-5.0

121.2

41

5.0

295.0

95

35.0

17.2

-30 -34.4

56.4

6

-14.4

85.9

24

-4.4

123.6

42

5.6

316.9

100 37.8

21.4

-25 -31.7

57.9

7

-13.9

87.8

25

-3.9

125.9

43

6.1

339.9

105 40.6

25.9

-20 -28.9

59.3

8

-13.3

89.7

26

-3.3

128.3

44

6.7

364.1

110 43.3

27.8

-18 -27.8

60.8

9

-12.8

91.6

27

-2.8

130.7

45

7.2

389.6

115 46.1

29.7

-16 -26.7

62.3

10 -12.2

93.5

28

-2.2

133.2

46

7.8

416.4

120 48.9

31.8

-14 -25.6

63.9

11

-11.7

95.5

29

-1.7

135.6

47

8.3

444.5

125 51.7

33.9

-12 -24.4

65.4

12

-11.1

97.5

30

-1.1

138.2

48

8.9

474.0

130 54.4

36.1

-10 -23.3

67.0

13 -10.6

99.5

31

-0.6

140.7

49

9.4

505.0

135 57.2

38.4

-8

-22.2

68.6

14 -10.0

101.6

32

0.0

143.3

50

10.0

537.6

140 60.0

40.7

-6

-21.1

70.2

15

-9.4

103.6

33

0.6

156.6

55

12.8

571.7

145 62.8

43.1

-4

-20.0

71.9

16

-8.9

105.7

34

1.1

170.7

60

15.6

607.6

150 65.6

45.6

-2

-18.9

73.5

17

-8.3

107.9

35

1.7

185.7

65

18.3

645.2

155 68.3

48.2

0

-17.8

75.2

18

-7.8

110.0

36

2.2

201.5

70

21.1

Temperature/Pressure Conversion Chart

All systems have a modulating capacity digital scroll compressor in Circuit A with a

digital compressor controller in the electric/control compartment. Circuit B has a digi-

tal scroll compressor controlled by staging. If equipped with an optional reheat circuit,

it is equipped with a modulating capacity digital scroll compressor with a separate

digital compressor controller in the electric/control compartment.
All compressors have crankcase heaters which must be powered up for 24 hours

prior to operating the compressor.

Compressors

3.7 Compressor

Operation,

Maintenance,

and

Replacement

WARNINGS

For your safety, wear eye protection, gloves, and protective

clothing when handling refrigerant and oil and when brazing.

Have a fire extinguisher nearby. See Hazard Levels, page 2.

DANGER

Never use oxygen to pressurize a refrigeration system. Oxygen

can explode on contact with oil and could result in personal

injury or death. When using high pressure gas such as nitrogen

for this purpose, ALWAYS USE A PRESSURE REGULATOR that

can control the pressure down to 1 or 2 psig. Failure to use a

regulator will result in extremely high pressure which could

exceed the burst pressure of the compressor or other system

components and result in personal injury or death. See Hazard

Levels, page 2.

DANGER

The refrigeration circuits are high pressure systems.

Hazards exist that could result in personal injury or death.

It is therefore required that the removal and installation of

these compressors be performed by a technician qualified

in R-410A refrigerant. See Hazard Levels, page 2.