beautypg.com

1 gas heat controls (cont'd) – Reznor YDSA Operation Manual User Manual

Page 34

background image

Form O-Y, PN 273647R1, Page 34

Gas Control Modulating (5:1, Option AG73 or 10:1, Option AG74 - applies to all models)

Sequence of Operation

1) W1 is energized and the DS1 control module verifies that the pressure switches are open.
2) Inducer (venter) is energized for pre-purge and the DS1 control module verifies that the low and high pressure

switches are closed.

3) After the pre-purge period has elapsed (20 seconds), the DS1 control module energizes the trial for ignition period

(17 seconds).

4) After blower-on delay (30 seconds from flame detected), the control will energize the blower (supply fan).
5) If W2 is energized, the high gas output will energize and the control will check for high pressure switch input.
6) After W1 and W2 are de-energized, the controller will run the blower-off delay (120 seconds) and return to standby

mode.

NOTE: For detailed information on the sequence of operation for the heat sections, refer to section 3.5 Heating

Staging Control, in the Model YDSA and YDHA Manual for Space Temperature Control System Options D19 (form

CP-Y-D19) or option D21 (form CP-Y-D21).

Venter

Assembly

Optional High Gas

Pressure Switch

Ignitor Limit

Dual Heat Section

Manifold Assembly

with Electronic

Modulation

Option AG74

Manifold Pressure Tap

Heat Section 2

2-Stg

Valve

Venter

Assembly

Optional

High Gas

Pressure

Switch

Manifold Pressure Tap

Heat Section 1

1-

Stg

Valve

Modulating

Valve

Venter Control

Pressure Switch

Optional

Low Gas

Pressure

Switch

Optional

Low Gas

Pressure

Switch

Optional High Gas

Pressure Switch

Ignitor

Venter

Assembly

Manifold Pressure Tap

Optional

Low Gas

Pressure

Switch

1-Stg

Valve

Modulating Valve

Venter

Control

Pressure

Switch

Single Heat

Section Manifold

Assembly with

Electronic

Modulation

Option AG73

FIGURE 25 - Furnaces with

Modulating Control Option

AG73 (5:1 control, single

heat section) and Option

AG74 (10:1 control, dual

heat sections)

NOTE: Heat sections

illustrated are standard

efficiency, non-condensing

furnaces. Controls for

condensing furnaces are the

same.

5.0 Maintenance/Service Procedures - Gas Heat Section (cont'd)

5.1 Gas Heat Controls (cont'd)